Aguato

    BOD and COD removal from industrial estate effluent by MBBR, sand and carbon filtration

    This common effluent treatment plant serves an integrated industrial estate at Haridwar in northern India. It was commissioned in 2008, is designed for 4500 m³/day and runs at full capacity; it was upgraded by inserting a moving bed biofilm reactor and dropping its physico-chemical treatment because the incoming effluent kept changing and its load kept rising. Raw effluent first passes a pump house with coarse and fine screens, an oil and grease trap and two equalization tanks with about 16.5 hours of retention, which lie upstream of the sampled section. The treated water is discharged to a river.

    Treatment line

    1. 01Rapid mixing and flocculation tankThe plant is run without any chemical addition.
    2. 02Two pre-settling tanks with tube settlersPrimary treatment holds the water about 2.6 hours.
    3. 03Moving bed biofilm reactor (MBBR)About 2.7 hours of retention.
    4. 04Aeration tank
    5. 05Secondary clarifierAbout 6.5 hours of retention.
    6. 06Pressure sand filter
    7. 07Activated carbon filterLast unit; sand and carbon filters together hold the water about 0.3 hours.

    What the source found

    Organic matter and suspended solids fell at every stage from pre-settling through the MBBR, clarifier and filters, and oil and grease met the discharge standard. Ammonia fell by 44% and total nitrogen by 19%, while phosphorus fell by 65%. Sand and carbon filtration were judged not enough for reuse; a laboratory test of coagulation, ultrafiltration and ozonation on the clarified effluent met non-potable reuse standards.

    Grab samples on two occasions in March and April 2018, taken after the equalization tank and after each treatment unit up to the carbon filter outlet.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    CODCODmg/L88343
    BODBODmg/L42611
    Total suspended solidsTSSmg/L4608
    pH7.17.6
    Oil and greaseO&Gmg/L75593%
    Ammonium nitrogenNH4-Nmg/L47.126.644%
    Total Kjeldahl nitrogenTKNmg/L53.340.225%
    Nitrate nitrogenNO3-Nmg/L1.64.10%
    Total nitrogenTNmg/L54.944.319%
    Orthophosphate as phosphorusPO4-Pmg/L3.22.328%
    Total phosphorusTPmg/L8.6365%
    ChlorideCl−mg/L653251%
    Sulfate as SO4SO42−mg/L18.98.555%
    FluorideF−mg/L0.80.6420%
    Sulfide as SS2−mg/L20.765%

    Inlet: equalisation tank. Outlet: outlet of the activated carbon filter. Grab samples in two campaigns in March and April 2018. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.