    COD and solids removal from electroplating estate wastewater by flocculation and tube settlers

    A common effluent treatment plant in an industrial area of Delhi, India, treats wastewater mainly from small electroplating and similar units, and discharges the treated water to a river. It was designed in the early 2000s for 12,000 m³/day of metal-bearing, low-organic wastewater, so it has no biological unit; the flow was 2,500 m³/day during sampling. To get some organic removal the operator doses a commercial bioculture into the equalisation tank and recirculates part of the sludge.

    Treatment line

    1. 01Preliminary treatment
    2. 02Equalisation tank8-hour retention; bioculture is dosed here.
    3. 03Pre-chlorination0.5-hour retention.
    4. 04Flocculation tank0.16-hour retention.
    5. 05Tube settlers0.25-hour retention.
    6. 06Post-chlorination0.3-hour retention.

    What the source found

    COD fell by 62% and suspended solids by 72%, while ammonia fell by only 13% and BOD stayed slightly above the discharge limit. The plant's low overall efficiency is put down to the lack of a biological unit.

    Grab samples at the plant inlet and final outlet in two campaigns between April and July 2017.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BODBODmg/Laround 12035 to 40
    CODCODmg/L34012862%
    Total suspended solidsTSSmg/L2687672%
    pH77.6
    Oil and greaseO&Gmg/L242.888%
    Ammonium nitrogenNH4-Nmg/L24.821.613%
    Orthophosphate as phosphorusPO4-Pmg/L4.12.734%
    ChlorideCl−mg/L1,05076028%
    Sulfate as SO4SO42−mg/L188.6127.532%
    FluorideF−mg/L0.40.175%
    Sulfide as SS2−mg/L6.111.7971%
    ZincZnmg/L0.550>99.9%
    CopperCumg/L1.150.0298%
    ChromiumCrmg/L0.64
    ManganeseMnmg/L0.210.250%
    NickelNimg/L1.551.1427%
    LeadPbmg/L0.210>99.9%
    CadmiumCdmg/L00

    Inlet: raw effluent at the plant inlet. Outlet: final treated effluent at the plant outlet. Grab samples in two campaigns between April and July 2017. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.