Nitrogen and phosphorus removal from sewage by anoxic-aerobic activated sludge and iron dosing
A small municipal treatment plant in Hungary serves roughly 7,500 population equivalent through a separate sewer, so its daily flow of about 810 m³/day stays fairly steady while the sewage is strong. The plant was studied to see how its operation could be changed in summer so that treated water keeps its nutrients for irrigation. Sludge is thickened and dewatered on site and taken to a larger plant, with no anaerobic digestion.
Treatment line
- 01Screens and sand trapsMechanical pre-treatment.
- 02Primary clarifierRemoves settleable solids; 38.5 m² surface and 3.5 m deep.
- 03Anoxic zonesThree mixed zones with a volume of 600 m³ for pre-denitrification, receiving nitrate recirculated from the last aerobic zone at about three times the inflow.
- 04Aerobic zonesThree aerated zones with a volume of 600 m³ for nitrification, run at a sludge age of about 21 days.
- 05Ferric dosingIron salt is added before secondary settling for chemical phosphorus removal.
- 06Secondary clarifierSeparates the activated sludge, which is returned to the biological stage; 77 m² surface and 4 m deep.
What the source found
Over the year the plant removed 95% of COD, 89% of total nitrogen and 97% of total phosphorus, nitrifying and denitrifying the high nitrogen load thanks to its long sludge age, and met the European Union discharge requirements. Model runs suggested that cutting the sludge age to about five days and stopping iron dosing in summer would still remove organic matter while keeping nitrogen and phosphorus in the water for irrigation, and that switching back to winter operation takes about a week.
Weekly samples of raw and treated wastewater over one year, plus online flow and temperature data, used to calibrate a computer model of the plant.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Flow | m3/d | 810 | |||
| COD | COD | mg/l | 980 | 45 | 95% |
| BOD | BOD | mg/l | 559 | ||
| Total suspended solids | TSS | mg/l | 588 | ||
| Total nitrogen | TN | mg/l | 88 | 9.8 | 89% |
| Total phosphorus | TP | mg/l | 14.9 | 0.52 | 97% |
| Alkalinity | Alk | mgCaCO3/l | 442 | 65 | 85% |
Inlet: raw sewage at the plant inlet. Outlet: treated effluent at the plant outlet. Annual averages of weekly samples over one year. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.