    BOD and solids removal from domestic sewage by an aerated attached-growth bioreactor

    A sewage treatment plant in Kacyiru sector, Gasabo District, Kigali, treating black and grey water from an estate of 100 buildings rehabilitated in 2016, with a capacity of 100 m³/day. The treated effluent is discharged into a wetland whose land is farmed for vegetables, sweet potatoes, maize, beans and sorghum.

    Treatment line

    1. 01Screen and grit channelInlet facility with one screen and grit channel.
    2. 02Primary sedimentation tank
    3. 03Attached-growth bioreactorAerobic reactor with two vertically mounted mechanical aerators.
    4. 04Secondary clarifierExcess sludge is returned to the aerobic tank.
    5. 05DisinfectionApplied to the clarifier effluent before discharge to the wetland.

    What the source found

    The plant removed about 51% of COD, 67% of BOD, 73% of suspended solids, 47% of total nitrogen and 61% of total phosphorus, which was judged low. The effluent did not meet the national discharge standard for turbidity, total nitrogen, total phosphorus, suspended solids, BOD and fecal coliforms, and pollution was higher downstream in the wetland than upstream.

    Six grab-sampling campaigns, every two weeks in 2019, at the plant inlet and outlet and at three points in the receiving wetland.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Temperature°C24.8324.08
    pH7.657.57
    TurbidityNTU568.994.5883%
    Total dissolved solidsTDSmg/l745.5841145%
    Total nitrogenTNmg/l64.7834.6147%
    Total phosphorusTPmg/l14.055.4162%
    Colourmg/l PtCo2,047.16738.6664%
    CODCODmg/l501.66248.2851%
    BOD5BOD5mg/l221.2573.4867%
    Total suspended solidsTSSmg/l511.75137.1673%
    IronFemg/l0.160.156.3%
    ManganeseMnmg/l0.040.050%
    CopperCumg/l0.060.0433%
    LeadPbmg/l0.020.0150%
    Total coliformsTCMPN/100ml241,960131,258.3346%
    Faecal coliformsFCMPN/100ml68,143.3342,973.3337%
    E. coliMPN/100ml36,043.3320,048.3344%

    Inlet: raw sewage at the plant inlet. Outlet: treated effluent at the plant outlet. Means of six grab-sampling campaigns every two weeks in 2019. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.