Aguato

    BOD and COD removal from city sewage by activated sludge with a biological phosphorus basin

    The plant in Mezitli district, Mersin province, removes carbon, nitrogen and phosphorus from the sewage of about 384,000 people, with a capacity of about 55,000 m³/day, and discharges to the sea through a deep-sea outfall. The sewers collect at or below sea level near the shore, and seawater is thought to enter the collection pit or sewer. Reuse of the treated water for farm irrigation was assessed.

    Treatment line

    1. 01ScreensRemove paper, wood, plastic and other solids.
    2. 02Sand and oil trap
    3. 03Pre-settlement tank
    4. 04Bio-phosphorus basinBiological phosphorus removal ahead of aeration.
    5. 05Aeration poolActivated sludge treatment to remove nutrients.
    6. 06Final settling tankSettled sludge is returned and the excess goes to mechanical sludge thickening.

    What the source found

    The plant removed about 95% of COD and BOD and 91% of suspended solids, but total nitrogen fell by only about 38% and total phosphorus by about 28%. The treated water did not meet the irrigation reuse criteria: its high conductivity, from sodium and chloride linked to seawater entering the sewers, ruled it out, and its BOD placed it in the lower reuse class.

    Inlet and outlet samples were analysed in duplicate at an accredited laboratory.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.117.39
    Electrical conductivityECµS/cm6,9206,430
    BODBODmg/L386.2518.4595%
    CODCODmg/L496.423.2195%
    ColiformCFU/100 mL0
    Suspended solidsTSSmg/L247.521.7991%
    Total phosphorusTPmg/L7.285.2528%
    Total nitrogenTNmg/L31.519.6638%
    Nitrate nitrogenNO3-Nmg/L17.8
    ChlorideCl−mg/L6,848457.79
    Active chlorineCl2mg/L0.79
    Total dissolved solidsTDSmg/L26.7 ± 6.12 in Table 2; 78 ± 15 in Table 4
    SodiumNamg/L321.1
    Sodium adsorption ratiomg/L26.7
    AluminiumAlmg/L<0.7
    ArsenicAsmg/L0.0550.04911%
    BerylliumBemg/L<0.0005
    CadmiumCdmg/L0.0380.02534%
    Hexavalent chromiumCr(VI)mg/L0.050.02942%
    CobaltComg/L<0.005<0.005
    CopperCumg/L0.0590.0548.5%
    FluorideF−mg/L<0.2
    IronFemg/L<0.2
    LeadPbmg/L0.250.17928%
    LithiumLimg/L<0.015
    ManganeseMnmg/L<0.05
    MolybdenumMomg/L<0.005
    NickelNimg/L0.260.1542%
    SeleniumSemg/L<0.005
    VanadiumVmg/L<0.001
    ZincZnmg/L0.110.25 ± 0.025 in Table 2; 0.025 ± 0.025 in Table 6

    Inlet: raw sewage at the plant inlet. Outlet: treated water at the plant outlet. One inlet and one treated water characterisation, each analysed in duplicate, given as mean and standard deviation. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.