Aguato

    Heavy metal removal from textile and domestic wastewater by biological and tertiary treatment

    A large plant for domestic and industrial wastewater in Prato, Tuscany, serving a textile district. It was built for a population equivalent of 900,000, has an average inflow capacity of about 100,000 m³/day, and about 70% of its inflow is industrial, mostly textile, partly delivered through a separate industrial sewer. Treated water goes to a surface water body and to a refining section for reuse in the textile district; the monitoring aimed to show that metals are removed by treatment rather than diluted by domestic sewage.

    Treatment line

    1. 01Coarse and fine bar screens
    2. 02Grit removal
    3. 03Primary sedimentationAlso receives the recycled secondary and tertiary sludge and the sludge line returns.
    4. 04Equalization
    5. 05Oxidation ditches with secondary settlersBiological oxidation and nitrification.
    6. 06Coagulation, flocculation and sedimentationTertiary treatment.
    7. 07OzonationFinal stage before discharge or reuse.

    What the source found

    Over the year the plant removed 66% of zinc but only 14% of boron, and metal levels in the effluent were within surface water discharge limits. Metals mostly bound to particles, such as zinc and chromium, left mainly with the sludge, while boron stayed dissolved and passed out with the treated water. The load of metal removed rose in line with the incoming load, so higher inputs did not reduce the plant's efficiency.

    Weekly 24 hour composite samples of the plant inlet and outlet over 12 months between October 2021 and October 2022, plus an eight-day intensive campaign in May 2022 that also sampled sludge; the figures used are from the 12-month campaign.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.96
    Total suspended solidsTSSmg/L126
    CODCODmg/L301
    BODBODmg/L124
    Total nitrogenTNmg/L36
    Nitrite nitrogenNO2-Nmg/L0.51
    Nitrate nitrogenNO3-Nmg/L2.35
    Ammonium nitrogenNH4-Nmg/L24
    Total phosphorusTPmg/L3
    ZincZnmg/L0.150.0567%
    CopperCumg/L0.05<0.0537%
    ManganeseMnmg/L0.040.05
    SeleniumSemg/L0.0070.003
    BariumBamg/L0.12<0.158%
    BoronBmg/L0.160.1413%
    Total chromiumCrmg/L0.040.01
    AntimonySbmg/L0.350.08
    LeadPbbelow the detection limit (0.05 mg/L)
    CadmiumCdbelow the detection limit (0.01 mg/L)
    NickelNibelow the detection limit (0.05 mg/L)
    ArsenicAsbelow the detection limit (0.02 mg/L)
    TinSnbelow the detection limit (0.02 mg/L)

    Inlet: raw wastewater at the plant inlet. Outlet: treated effluent at the plant outlet. Means of weekly 24 hour composite samples over 12 months, October 2021 to October 2022. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.

    Similar references