BOD and COD removal from city sewage by anaerobic and facultative stabilization ponds
A city's first large sewage treatment plant at Hodeidah, commissioned in 2017, treats mainly domestic sewage in waste stabilization ponds covering 22 ha, with water flowing by gravity from inlet to outlet. Pharmaceutical, food processing and service station discharges also reach the sewer. The treated water is assessed for reuse in irrigation, such as the city's green belt.
Treatment line
- 01Anaerobic pondMeant to take the high organic load; heavy sludge has built up with no desludging, and it is under-designed for the current load.
- 02Facultative pondsTheir outflow is the plant effluent; the ponds were pink and gave off odour, signs of overloading and mostly anaerobic conditions.
What the source found
In that sampling the ponds removed 77% of COD, 81% of BOD and 53% of suspended solids; across six samplings from 2020 to 2021, COD removal ranged from 24% to 84% and BOD removal from 74% to 85%. Sludge build-up and an undersized anaerobic pond are the main causes of the weak effluent, so enlarging the pond or adding a second one, regular desludging and a further pond stage as tertiary treatment are recommended. The effluent is judged usable for irrigation.
Raw sewage and pond effluent were sampled twice a month between 9 and 10 am and analysed in the plant's own laboratory; the figures shown are from one sampling in July 2021.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 7.6 | 8.8 | |||
| Electrical conductivity | EC | µS/cm | 5,370 | 5,970 | |
| Total dissolved solids | TDS | mg/l | 3,490 | 3,880 | 0% |
| Suspended solids | TSS | mg/l | 380 | 180 | 53% |
| COD | COD | mg/l | 757 | 175 | 77% |
| BOD5 | BOD5 | mg/l | 450 | 84 | 81% |
Inlet: raw sewage at the plant inlet. Outlet: effluent of the facultative ponds. One sampling in July 2021; the text dates the last analysis 21 July and the removal table dates it 3 July. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.