    Nitrogen and phosphorus removal from domestic sewage in a warm climate by an oxidation ditch

    A municipal plant in Phuket Province, southern Thailand, treats domestic sewage in an oxidation ditch run as extended activated sludge for biological nutrient removal. It was designed for about 28,000 m³/day and the temperature is around 30 °C all year. Each house, hotel and apartment served has its own septic tank or grease trap, which may help explain the weak incoming sewage.

    Treatment line

    1. 01Oxidation ditchAnoxic zone for denitrification and aerobic zone for nitrification, each with a 24 h retention time and a 15 day sludge age, 30 days in total; no anaerobic tank.

    What the source found

    Ammonia fell by 45%, and incomplete ammonia removal was put down to occasional shortage of oxygen, as the plant has no online oxygen control. Phosphorus fell by 75%. The incoming sewage carried enough organic matter for denitrification and phosphorus uptake, and nutrient removal was not much different from a comparable plant in a cold climate.

    Daily inlet and outlet samples over one year, reported as 2013 averages, with dissolved oxygen checked in both zones by meter.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BODBODmg/L1743.798%
    Ammonium nitrogenNH4-Nmg N/L15.98.745%
    Total nitrogenTNmg N/L25.38.7
    Nitrate nitrogenNO3-Nmg N/L3.2
    Total phosphorusTPmg P/L3.60.975%

    Inlet: raw sewage entering the oxidation ditch plant. Outlet: final effluent of the oxidation ditch plant. Yearly averages of daily samples for 2013. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.