Meeting COD and suspended solids limits by shortening lagoon polishing after activated sludge
A municipal sewage treatment plant in Thiès, Senegal, fed by a separate sewer of 75 km and designed for 3,000 m³ a day, running at a little over half that. After eleven years the outlet of its tertiary lagoons no longer met the national discharge standard because algae raised suspended solids, BOD and COD. Raw sewage first passes a grit and oil removal chamber; the treated water goes to a lake used for market gardening.
Treatment line
- 01Activated sludgeThe main biological treatment line.
- 02ClarifierIts outlet flowmeter is used to measure the flow entering the plant.
- 03Natural lagoonsEight lagoons of 22,000 m³ in total in two parallel lines of settling, facultative and maturation ponds, about 28 days retention at design flow; from 2018 one line of four was taken out of service to halve the retention time.
What the source found
Running all the water through one line of four lagoons brought suspended solids and COD back within the standard, and in 2019 the plant removed about 94% of suspended solids, 96% of BOD, 95% of COD, 81% of total nitrogen and 77% of phosphorus. BOD stayed slightly above the limit because of algae and nitrogen did not meet its limit, while bacteria fell by about four log units. A dumping of expired food products in April 2019 and a raw sewage bypass to the lagoons during heavy rain in August 2019 disturbed the results.
Twice-weekly samples from 2018 to the end of 2019: a flow-proportional composite of hourly samples after the grit and oil chamber, and a grab sample at the lagoon outlet, summarised as monthly and annual means; the figures shown are the 2019 annual means.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 7.76 | 8.54 | |||
| Total suspended solids | TSS | mg/L | 679.8 | 38 | 94% |
| BOD5 | BOD5 | mg/L | 1,009.5 | 42.8 | 96% |
| COD | COD | mg/L | 1,748.3 | 91.3 | 95% |
| Total nitrogen | TN | mg/L | 199.1 | 38.3 | 81% |
| Total phosphorus | TP | mg/L | 37 | 8.4 | 77% |
| Bacteria (indicator organism not named in the table) | CFU/100 mL | 9.7 × 10^6 | 1.75 × 10^3 | 99.9% |
Inlet: raw sewage after grit and oil removal. Outlet: outlet of the lagoons. Annual means for 2019 of twice-weekly samples. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.