    COD and solids removal from high-altitude sewage by anaerobic, facultative and maturation ponds

    The sewage plant of Pucará, in Lampa province, Puno, Peru, lies at about 3,890 m and discharges to the local river. It is a pond system whose effluent exceeds the national limits, put down to a design poorly suited to the cold local climate.

    Treatment line

    1. 01Screens and grit chamberPreliminary treatment.
    2. 02Anaerobic pond
    3. 03Four facultative ponds in parallelEach feeds its own maturation pond; average depth with the maturation ponds about 0.8 m, shallower than usual, which shortens the retention time.
    4. 04Four maturation pondsOne after each facultative pond; their outlets join into the plant effluent.

    What the source found

    COD fell by 67% and suspended solids by 58% across the whole plant. The effluent still exceeded the national limits for BOD, COD and thermotolerant coliforms, while suspended solids and oils and grease were within them. Low temperatures, shallow ponds, poor design and lack of operation and maintenance were blamed, and a moving bed biofilm reactor was proposed as the solution.

    Samples at every stage, from the inlet to the outlet of each pond line, once in the wet season and once in the dry season of 2023; the figures are the average of the two.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Total suspended solidsTSSmg/l348.48146.4958%
    CODCODmg/l1,263.5414.167%
    Oil and greaseO&Gmg/l15.79.2541%
    BODBODmg/l505.4194.562%
    Thermotolerant coliformsFCMPN/100 mL22,050,0003,762,50083%

    Inlet: raw sewage entering the preliminary treatment. Outlet: plant effluent after the maturation ponds. Averages of one wet season and one dry season sampling in 2023. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.