Aguato

    BOD and suspended solids removal from municipal sewage by extended-aeration activated sludge

    A municipal sewage works in Jordan, running since 2011 and designed for 10,000 m³/day, received about 4000 m³/day during the study. Treated sewage in the country goes mainly to restricted farm irrigation, with any surplus released to valleys and dams. On site, the screens, grit chamber, both anaerobic phosphorus-removal tanks, one aeration tank, the sand filters and the equalisation tank were out of service, so the water passed only through the units listed.

    Treatment line

    1. 01Extended-aeration activated sludge tankOne aeration tank in service; sludge age of 13 to 20 days.
    2. 02Final sedimentation tankOnly one of the secondary settling tanks was working; excess sludge goes to drying beds and dewatering.
    3. 03Chlorine disinfectionOperated only intermittently.

    What the source found

    Even with much of the works out of service, the plant removed about 96% of BOD and COD and 98% of suspended solids, and the treated water was judged suitable for irrigating fruit trees and green areas. Modelling showed the current layout would not cope with expected growth in flow, and that bringing the idle settling tanks and aeration tank back into use would keep the effluent within standards up to the design flow.

    Inlet and outlet samples taken in the morning over six months, July to December, with the six-month averages compared; a process model was then built to test future layouts.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BODBODmg/L984.436.996%
    CODCODmg/L1,198.850.696%
    Total suspended solidsTSSmg/L996.916.498%
    Total dissolved solidsTDSmg/L2,032.9970.852%
    Inflowm3/day4,000
    Dissolved oxygenDOmg/L1.31.91
    pH7.57.2
    Temperature°C17.928

    Inlet: raw wastewater at the plant entrance. Outlet: treated effluent at the plant outlet. Six-month averages, July to December, of morning samples taken twice a week. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.