Aguato

    BOD and COD removal from municipal sewage for irrigation reuse by extended aeration

    A municipal plant north-west of Irbid, commissioned in 1987, that treats sewage from the city and surrounding communities. In 2022 it received an average of 9,323.5 m³ per day, against a first-stage design capacity of 13,358 m³ per day. The treated effluent goes mainly to agricultural reuse under the national reclaimed water standard.

    Treatment line

    1. 01Screening
    2. 02Grit removal
    3. 03Extended aeration activated sludge
    4. 04Secondary clarification

    What the source found

    Removal averaged 97% for BOD, 96% for COD and 96% for suspended solids over the twelve months, and every monthly effluent value met the national reuse requirements. A process model calibrated on the same data predicted effluent BOD well but predicted much cleaner effluent COD and suspended solids than the plant produced, so it was judged reliable for BOD only.

    Weekly grab samples of inlet and outlet over 2022, 96 at each point, averaged by month; the data were also used to calibrate a process model.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BOD5BOD5mg/L1,094.827.498%
    CODCODmg/L1,697.669.496%
    Total suspended solidsTSSmg/L600.52197%

    Inlet: raw wastewater at the plant inlet. Outlet: treated effluent at the plant outlet. Annual means of twelve monthly means of weekly grab samples in 2022. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.