Aguato

    Meeting discharge limits for BOD and suspended solids in city sewage by biological treatment

    The second extension of a large sewage works on the east side of Baghdad, in operation since 1984 with a design capacity of 300,000 m³/day but receiving about 450,000 m³/day from around 1.5 million people. It is one of three parts of the works, and the treated water is discharged to a river.

    Treatment line

    1. 01Biological treatmentDesigned to remove organic matter, not dissolved matter.

    What the source found

    This part of the works removed about 93% of BOD, 88% of COD and 90% of suspended solids on average, and its average effluent quality was within the national discharge limits. The ratio of BOD to COD in the treated water was still higher than typical for well treated sewage, which suggests the effluent needs further treatment.

    Plant records from March to December 2011, reported as monthly averages, with one inlet figure for the whole works and an outlet figure for each of its three parts.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BOD5BOD5ppm235.3915.7793%
    CODCODppm361.0943.0788%
    Total suspended solidsTSSppm245.1623.6790%
    pH7.187.37
    ChlorideCl−ppm324.25273.7616%

    Inlet: raw sewage at the inlet of the works. Outlet: treated effluent of this part of the works. Averages of monthly values from March to December 2011. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.