Aguato

    Removing emerging contaminants and BOD from city sewage by settling and stabilization ponds

    The largest sewage plant in Indonesia, in Bandung, West Java, serving the eastern part of the city at an operating capacity of 40,000 m³/day against a listed total of 80,000 m³/day. The treated water goes to the largest river of the province, which flows to a reservoir seen as a possible future water source for the city.

    Treatment line

    1. 01Bar screens
    2. 02Mechanical screens
    3. 03Primary sedimentationThe primary treatment has a retention time of 1.5 to 2 hours.
    4. 04Anaerobic pondsPart of the secondary treatment by waste stabilization ponds.
    5. 05Facultative ponds
    6. 06Maturation ponds

    What the source found

    The plant removed about 70% of BOD, 63% of suspended solids and 48% of COD, and its effluent met the national discharge limits for domestic sewage. The modest COD removal is put down to sludge building up in the ponds, which are desludged irregularly. Overall the plant removed more than 98% of the detected emerging contaminants, with easily degraded drugs largely removed while a few persistent compounds passed through or even rose.

    Total nitrogen and phosphorus are from 24-hour composite samples at the plant inlet and outlet on one dry-weather day in June 2019; suspended solids, BOD, COD and ammonia are from the plant's weekly monitoring from January to June 2019.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.68.4
    Total suspended solidsTSSmg/L642463%
    BODBODmg/L902770%
    CODCODmg/L1739048%
    Total organic carbonTOCmg/L16.85.567%
    Total nitrogenTNmg/L11.52.677%
    Total phosphorusTPmg/L0.50.420%
    Ammonia nitrogenNH3-Nmg/L8.43.163%
    Trimethoprimng/L1823183%
    Clarithromycinng/Lnot detectednot detected
    Sulfamethoxazoleng/Ldetected, not quantifiednot detected
    Sulfamethazineng/L25below limit of detection
    Acetaminophenng/L9,111below limit of detection
    Naproxenng/Lnot detectednot detected
    Diclofenacng/Lnot detectednot detected
    Ibuprofenng/L2,315below limit of detection
    Triclosanng/L470below limit of detection
    Atenololng/Lnot detectednot detected
    Metoprololng/Lnot detectednot detected
    Carbamazepineng/L1223
    Fluoxetineng/L108
    Benzotriazoleng/Lbelow limit of quantification92
    Bisphenol Ang/L378below limit of quantification
    Caffeineng/L12,220below limit of quantification
    DEETng/L4,9688298%
    Atrazineng/Lnot detectednot detected
    Tris(2-chloroethyl) phosphateng/L101251
    Metforminng/Ldetected, not quantifiednot detected
    Estroneng/Lnot detectednot detected
    N-nitrosodimethylamineng/Lnot detectednot detected

    Inlet: raw wastewater at the plant inlet. Outlet: final effluent of the pond system. Solids, BOD, COD and ammonia are plant monitoring averages from January to June 2019; the other rows are 24-hour composite samples from one dry-weather day in June 2019, analysed in duplicate. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.