Aguato

    Polishing UASB-treated sewage for BOD and suspended solids in final polishing ponds

    A sewage works in Noida, India, with a capacity of 27,000 m³/day treats sewage through screens, grit chambers and upflow anaerobic sludge blanket reactors, then sends the reactor effluent to final polishing ponds. Only the polishing ponds are described here.

    Treatment line

    1. 01Final polishing pondsTwo ponds of 110 by 120 m and 1.6 m deep, with a design retention time of 1.6 days.

    What the source found

    The ponds removed about a third of BOD and about half of suspended solids and ammonium. The removal of BOD, COD and solids is put down mainly to settling. The polishing ponds studied did not meet the BOD and suspended solids disposal standards; they were judged poorly designed and acting mainly as clarifiers.

    Grab samples on one day in October 2010 at seven points along the ponds, from the inlet channel to the final effluent.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Temperature°C29.728.4
    pH7.28.1
    Alkalinity as CaCO3Alkmg/L7006487.4%
    BODBODmg/L724833%
    CODCODmg/L20811843%
    Total suspended solidsTSSmg/L1789149%
    Volatile suspended solidsVSSmg/L1013664%
    Ammonium nitrogenNH4-Nmg/L49.32451%
    Nitrate nitrogenNO3-Nmg/L34.60%
    Orthophosphate as phosphorusPO4-Pmg/L4.23.614%
    Redox potentialORPmV-331.2-40.2
    Dissolved oxygenDOmg/L0.9617.28
    SulfideS2−mg/L240>99.9%
    SulfateSO42−mg/L47580%

    Inlet: inlet channel to the polishing ponds. Outlet: final effluent of the polishing ponds. Grab samples on one day in October 2010. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.