Aguato

    COD and BOD removal from town sewage by sand trap, activated sludge and secondary clarifier

    A small municipal sewage works for the town of Ljubuški in the south of Bosnia and Herzegovina, built for secondary treatment of 6,000 population equivalent and fed by gravity from a combined sewer. Treated water is discharged to a nearby river. Raw sewage first passes a coarse grid and a fine grid before the sampled section below.

    Treatment line

    1. 01Fine sieve with press3 mm sieve.
    2. 02Aerated sand trap
    3. 03Bio-aeration basin1,156 m³ activated sludge basin aerated by submerged bottom blowers.
    4. 04Secondary clarifierPart of the settled sludge returns to the basin; the rest goes to a thickener and drying beds.
    5. 05DisinfectionUsed only when needed before discharge.

    What the source found

    On the 2019 averages the works removed about 95% of COD and 98% of BOD, met every discharge limit and the required minimum reductions, and did better than in 2018. Sludge settling was poor at times, with sludge age, food to biomass ratio and retention time often outside the usual range, and the retention time should be raised. The works runs below its design load and uses about 0.455 kWh of electricity per m³ treated.

    24-hour composite samples taken by an automatic sampler behind the fine grid and at the outlet shaft, 18 times in 2018 and 19 times in 2019; the removal figures are from the 2019 averages.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    CODCODmg/L563.2127.6695%
    BOD5BOD5mg/L270.635.9598%
    Total suspended solidsTSSmg/L178.114.78
    BOD5 to COD ratio0.510.23

    Inlet: raw sewage behind the fine grid. Outlet: treated effluent at the outlet shaft. Averages of 19 24-hour composite samples taken in 2019. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.