    Silt density index from a plugging test

    The silt density index is the standard fouling screen for membrane feed water: a 0.45 µm filter at 207 kPa, two timed 500 mL samples, one number.

    15 min is the common standard; use 5 or 10 min if the filter plugs before then.
    Silt density index
    5.33

    Above the limit: pretreatment required (media or membrane filtration, coagulation).

    Plugging
    80.0%
    Limit for this membrane
    3
    • Plugging above 75%: repeat with a shorter test duration.

    How it works

    From the two timed 500 mL samples and the elapsed test time in minutes:

    SDI=100(1−titf)t(1)
    where
    SDI
    silt density index, % per minute
    ti
    time to filter the first 500 mL, min
    tf
    time to filter the final 500 mL, min
    t
    elapsed test time, min

    Test conditions: 0.45 µm filter, 47 mm diameter, 207 kPa constant pressure, dead-end flow. Recommended maxima: nanofiltration 0 to 3, hollow-fibre RO 0 to 2, spiral-wound RO 0 to 3; manufacturers accept 4 to 5 at most. SDI is a static two-point measure in dead-end mode and misses colloids below 0.45 µm, so it predicts cross-flow fouling only loosely.

    Related reading

    These calculators use standard published formulas and are provided for preliminary engineering guidance. Confirm against measured data and vendor projections before design. Model your full water matrix in Nepti or post your project to compare provider proposals.