COD and colour removal from knit textile wastewater by moving bed and membrane bioreactors
Real wastewater from a knit composite textile factory in Tongi, Bangladesh, was treated in a small two-compartment reactor with an effective volume of 130 litres. The aim was to cut the pollutant load with biofilm treatment followed by membrane filtration. No coagulant was added.
Treatment line
- 01Moving bed bioreactor89 litre aerated compartment holding plastic biofilm carriers, mixed by coarse bubble diffusers.
- 02Membrane bioreactor41 litre aerated compartment with a submerged hollow fibre membrane of 1 m² and 0.03 µm pores, installed on day 45, with fine bubble aeration to scour the membrane.
What the source found
Once the membrane was in place, COD removal averaged 89 to 93%, colour removal 83 to 87% and turbidity removal 96%, all at a one-day retention time. Zinc and chromium ended below the national discharge limit, while lead stayed slightly above it and iron above it. Removing colour without a tertiary treatment step was judged a viable approach.
A 220-day continuous run in which the hydraulic retention time was cut from 5 days to 2.5 days and then to 1 day once the membrane was installed, with organics, colour, solids and turbidity tracked over time and four heavy metals measured at inlet and outlet on days 50, 100, 150 and 200. The metal figures are from the day 200 sampling.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| COD | COD | mg/L | 1302.05 to 1671.11 | 140.97 to 182.31 | |
| BOD | BOD | mg/L | 709.10 to 974.43 | 39.78 to 65.95 | |
| Colour | mg Pt-co/L | 608 to 812 | 91.13 to 138.96 | ||
| Total suspended solids | TSS | mg/L | 0 to 10.11 | ||
| Turbidity | NTU | 108 to 163 | 2 to 7 | 96% | |
| Total chromium | Cr | mg/L | 1.32 | 0.2 | 85% |
| Zinc | Zn | mg/L | 23 | 0.92 | 96% |
| Iron | Fe | mg/L | 85.23 | 10.04 | 88% |
| Lead | Pb | mg/L | 1.33 | 0.14 | 90% |
Inlet: raw textile wastewater fed to the reactor. Outlet: permeate of the membrane bioreactor. Organics, colour, solids and turbidity are ranges over the period after the membrane was installed (days 46 to 220); metals are single measurements on day 200. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.