Reclaimed water from sewage by anaerobic, anoxic and aerobic tanks with membrane filtration
A municipal sewage plant in São Paulo State serving about 175,000 inhabitants treats an average of about 360 litres per second with a hydraulic retention time of 6 hours. Its permeate is stored as reclaimed water and pumped into tanker trucks, with the surplus discharged to a river.
Treatment line
- 01Preliminary treatment
- 02Anaerobic tankFirst of the biological reactors that remove organic matter and nutrients.
- 03Anoxic tank
- 04Aeration tank
- 05Membrane tankUltrafiltration of the mixed liquor by hollow-fibre membranes with a nominal pore size of 0.04 µm and about 72,000 m² of filtration area.
- 06Treated effluent tankHolds the reclaimed water before it is pumped to tanker trucks.
What the source found
The reclaimed water was of good quality for conventional parameters, with BOD and suspended solids removal above 99%, and readily biodegradable pharmaceuticals such as paracetamol, caffeine and ibuprofen were removed by more than 90% on average. Diclofenac and propranolol were only partly removed, and carbamazepine and its metabolites passed through almost unchanged, so extra polishing such as ozonation or activated carbon may be needed depending on the reuse.
Fourteen monitoring campaigns with 24 hour composite samples at the plant inlet and outlet and grab samples from the anaerobic, anoxic, aeration and membrane tanks, alongside the plant's own routine monitoring of conventional parameters over the same period.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| BOD | BOD | mg/L | 373 | < 1 | |
| Total Kjeldahl nitrogen | TKN | mg-N/L | 70.5 | 0.9 | 99% |
| Nitrate nitrogen | NO3-N | mg-N/L | 7.8 | ||
| Phosphate as phosphorus | PO4-P | mg-P/L | 8 | 2 | |
| Total suspended solids | TSS | mg/L | 314 | < 2.5 | |
| Turbidity | NTU | 0.2 |
Inlet: raw sewage at the plant inlet. Outlet: reclaimed water leaving the membrane bioreactor plant. Averages of the plant's routine monitoring over the same period as the fourteen research campaigns. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.