Aguato

    BOD and suspended solids removal from domestic wastewater by anaerobic reactors and a wetland

    An integrated biological treatment plant at an industrial company's site treats the site's domestic wastewater from bathrooms, washing and ablution, with no catering, which keeps its organic load lower than at a comparable hotel plant. Treatment of such wastewater from business activities is required by national regulation.

    Treatment line

    1. 01Upflow anaerobic sludge blanket reactorFirst anaerobic stage, fed by an influent pump that runs 16 hours a day.
    2. 02Up-flow anaerobic reactorSecond anaerobic stage.
    3. 03WetlandServed by a circulation pump that runs around the clock.

    What the source found

    The plant removed 89% of BOD, 78% of COD and 86% of suspended solids, less organic matter than a similar plant with an added aerobic stage, but it needs fewer units, only pumps and no blowers, and less attention from operators. Most of its estimated carbon emissions come from the anaerobic breakdown of organic matter rather than from electricity use.

    Samples taken at the plant inlet and outlet and analysed for organic matter, suspended solids, oil and grease, coliforms, detergents and pH, alongside a review of operation and an estimate of carbon emissions.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BOD5BOD51151389%
    CODCOD24053.778%
    Total suspended solidsTSS66986%
    Oil and greaseO&G<2.38<2.38
    Total coliformsTC16,00024099%
    Surfactants (MBAS)0.8<0.0791%
    pH7.17.4

    Inlet: wastewater at the plant inlet. Outlet: treated water at the plant outlet. Inlet and outlet samples of the plant analysed for the study; the source does not give the number of samples or the date. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.