    Sanitary wastewater BOD and COD removal by anaerobic baffled and moving bed biofilm reactors

    The domestic wastewater plant of a cement and refractory brick factory in Indonesia, treating sanitary, prayer room and floor cleaning water from staff and visitors. It is planned for 6.91 m³ a day with room for 8 m³ a day, but receives only about 1 to 2 m³ a day. Black water first passes two septic tanks, whose overflow joins the grey water in the biofilter tank, and the treated water is released to a drain.

    Treatment line

    1. 01Anaerobic baffled reactorVertical baffles force the water down and up through each compartment; nutrients (dextrose and molasses) and a bacterial culture are added weekly.
    2. 02Moving bed biofilm reactorAerobic stage with plastic carrier media for biofilm growth, aerated by a blower.

    What the source found

    The two-stage biofilter removed about 76% of BOD and 68% of COD, and both met the national discharge standard. Ammonia stayed slightly above its limit, which was put down to the blower sometimes stopping long enough for dissolved oxygen to drop and nitrification to suffer. The very low inflow gives a long retention time, which needs watching to avoid overly septic conditions.

    One accredited laboratory test of the water before and after the biofilter units, taken in May 2025.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    BODBODmg/l591476%
    CODCODmg/l1053468%
    AmmoniaNH3mg/l2210.751%

    Inlet: wastewater at the inlet of the biofilter units. Outlet: treated water at the outlet of the biofilter units. One accredited laboratory test in May 2025. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.