    Nutrient removal from sewage of 30,800 people by activated sludge and chemical precipitation

    The largest of five municipal treatment plants studied in the metropolitan area of Vienna, serving about 30,800 connected inhabitants, designed for 140,500 population equivalents with an average loading of about 78,400. It receives on average 18,700 m³/day through a pressure pipe from a combined sewer system, and wine production in the catchment may affect the raw wastewater in season. Phosphorus removal is required for sensitive areas under EU rules.

    Treatment line

    1. 01Mechanical treatmentPrimary mechanical step ahead of the biological stage.
    2. 02Activated sludge with nitrification and denitrificationRemoves organic carbon and nitrogen.
    3. 03Chemical phosphorus precipitationPhosphorus is precipitated with iron or aluminium salts, or both.

    What the source found

    Over the year the plant removed 96% of COD, 79% of total nitrogen and 94% of phosphorus. Across the five conventional plants studied, whose results were pooled, genetic markers of human faecal pollution were still found in high concentrations in the treated effluent.

    Daily plant data from 24-hour flow-proportional samples, cross-checked by the researchers' own 24-hour composite samples of raw and treated wastewater taken every 4 to 6 weeks over one year; the figures are medians.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    CODCODmg/L4411696%
    Total phosphorusTPmg/L50.394%
    Total nitrogenTNmg/L43979%
    Nitrate nitrogenNO3-Nmg/L4
    Ammonium nitrogenNH4-Nmg/L0.1

    Inlet: raw wastewater at the plant inlet. Outlet: treated wastewater at the plant outlet. Medians over one year of 24-hour flow-proportional composite samples. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.