Landfill leachate treatment by coagulation, anaerobic membrane bioreactor and reverse osmosis
A municipal solid waste landfill in a seasonal valley about 35 to 40 km east of Jeddah produces a very strong, mature leachate. After the site's waste sorting facility closed, untreated leachate built up, overloading the collection network and seeping from the cells, and the existing treatment plant does not meet national discharge limits. A computer model of the existing plant, set up for 700 m³/day, was used to compare it with four upgrade options.
Treatment line
- 01Coagulation and flocculationChemical treatment at the head of the plant.
- 02Primary clarifier
- 03Equalization tanks
- 04Anoxic tank
- 05Anaerobic membrane bioreactor
- 06Disinfection
- 07Reverse osmosisFinal polishing step, which receives too high a pollutant load from the biological stage.
What the source found
In the one measured inlet and outlet pair the plant removed about 83% of COD. In the model the existing plant fails the discharge standards for the main organic and nitrogen parameters because its biological stage removes too little organic matter and nitrogen, leaving the reverse osmosis unit overloaded. Of five modelled options, a three-compartment aerobic and anoxic membrane bioreactor followed by reverse osmosis gave the best balance of compliance, footprint and moderate operating cost, while options built around advanced oxidation cost the most to run.
Leachate samples taken at the landfill and analysed in a laboratory were used to calibrate a process simulation model, which then predicted effluent quality and costs for the existing plant and four upgrade scenarios. The COD removal figure is from the one sampling that had a measured plant effluent.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| COD | COD | mg/L | 27,000 | 4,700 | 83% |
| BOD | BOD | mg/L | 2,165 | 2,350 | 0% |
| Ammonia nitrogen | NH3-N | 800 | 300 | ||
| Nitrate | NO3− | 33.9 | 0.37 | 99% | |
| Total nitrogen | TN | 952 | 672 | ||
| Total phosphorus | TP | 56.6 | 5.78 | ||
| pH | 8.1 | 7 | |||
| Dissolved oxygen | DO | 0.37 | 2.75 |
Inlet: raw landfill leachate entering the plant. Outlet: measured effluent of the existing plant. One leachate sampling with a measured plant effluent, used to calibrate the process model. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.