    Ammonia and COD removal from landfill leachate by a sequencing batch reactor and a reed bed

    A large domestic waste landfill in the New Forest, Hampshire, in southern England, has a leachate treatment plant built to nitrify strong methanogenic leachate. It can treat up to 150 m³/day and usually treated 50 to 70 m³/day, limited by how much leachate could be pumped from the site. Treated leachate goes to the public sewer and on to a small rural sewage works, which could not have taken raw leachate.

    Treatment line

    1. 01Raw leachate balance tankCovered reinforced concrete tank from which raw leachate is pumped.
    2. 02Sequencing batch reactorCovered, insulated aeration tank with venturi aerators and automatic alkali dosing for pH, kept warm to nitrify through the winter.
    3. 03Treated leachate balancing tankUncovered concrete tank receiving the decanted treated leachate.
    4. 04Reed bedSubsurface flow bed of 800 m², planted with reeds, polishing the effluent before the sewer.

    What the source found

    Overall removal of ammoniacal nitrogen was above 99%, with the reed bed further lowering what remained after the reactor. COD fell by 67% and always stayed well inside the sewer consent, BOD in the final effluent stayed consistently low, and nitrate rose as the ammonia was nitrified. The plant was treating more than 80 m³/day within four weeks of start-up.

    Mean values for 2003 of the raw leachate, the reactor effluent and the final effluent after the reed bed, from monitoring since commissioning in January 2003.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    CODCODmg/l94230967%
    BOD5BOD5mg/l723
    Ammoniacal nitrogenNH3-Nmg/l8200.4899.9%
    Alkalinity as CaCO3Alkmg/l3,8301,13870%
    Nitrate nitrogenNO3-Nmg/l0.213840%
    Nitrite nitrogenNO2-Nmg/l0.040.870%
    ChlorideCl−mg/l1,5021,5070%
    pH7.68.4

    Inlet: raw leachate. Outlet: final effluent after the reed bed. Mean values for 2003. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.