COD and nitrogen removal from leachate by sequencing batch reactors and reverse osmosis
The leachate treatment plant of a sanitary landfill serving the Thessaloniki metropolitan area in Greece, in operation since 2008 and receiving 1,000 to 1,200 tonnes of waste a day. During the study the landfill produced about 350 m³ of leachate a day. The reverse osmosis permeate is discharged to a nearby stream, while the reverse osmosis concentrate is reduced in two vapour recompression evaporators and returned to the landfill.
Treatment line
- 01Grit removal
- 02Primary sedimentationNo coagulant is added.
- 03Four parallel sequencing batch reactors2,100 m³ each on an 8-hour cycle of aerobic and anoxic periods for nitrification and denitrification, 17.5 days retention, with glycerol from biodiesel production added as a carbon source.
- 04Discharge tankSettles the reactor effluent before the supernatant goes on.
- 05Sand filter
- 06Cartridge filters10 µm nominal pore size.
- 07One-stage reverse osmosisDisc-tube modules with brackish water membranes, 15.5 m³/h capacity, run at 30 to 40 bar.
What the source found
The reactors removed most BOD and ammonium but only part of the COD and total nitrogen, and suspended solids rose across them because the sludge settled poorly. After reverse osmosis the whole line removed about 99% of COD, BOD and total nitrogen and the effluent met the discharge requirements. The evaporators treating the concentrate used more than half of the plant's energy and gave a large share of its greenhouse gas emissions.
Weekly samples over two years at the inlet, after primary treatment, after the reactors and in the reverse osmosis permeate, with energy use calculated from the installed equipment and its operating hours.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Electrical conductivity | EC | µS/cm | 23,015 | 405 | |
| pH | 7.5 | 7.3 | |||
| Total suspended solids | TSS | mg/L | 166 | 4 | 98% |
| COD | COD | mg/L | 3,286 | 15 | 99.5% |
| BOD5 | BOD5 | mg/L | 909 | 11 | 99% |
| Total nitrogen | TN | mg/L | 1,360 | 15 | 99% |
| Ammonium nitrogen | NH4-N | mg/L | 941 | <1 | >99.9% |
Inlet: raw leachate at the plant inlet. Outlet: reverse osmosis permeate. Means of weekly samples over two years. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.