Arsenic removal from well water by prechlorination, iron co-precipitation and pressure filters
The treatment system supplies drinking water to 264 residents of Climax, Minnesota, from two wells about 43 m deep in a buried artesian aquifer, and the water is also fluoridated and stored in a water tower. Most of the arsenic in the well water is in its reduced form and the water carries natural iron and manganese, so the system was installed to bring arsenic below the new drinking water limit. It was evaluated over one year from August 2004 to August 2005.
Treatment line
- 01PrechlorinationChlorine, gas at first and sodium hypochlorite from January 2005, oxidizes arsenic and iron so they form iron solids.
- 02Supplemental iron additionFerric chloride dosed after the chlorine point from January 2005, because the natural iron was not enough.
- 03Two contact tanksTwo tanks of about 1.3 m³ each in parallel, upflow, giving 5 minutes for iron flocs to form.
- 04Two pressure filtersTwo parallel downflow vessels, each with a bed of about 0.6 m of ceramic filter media at a high filtration rate, backwashed automatically with treated water.
What the source found
Before iron was added, arsenic in the treated water averaged above the drinking water limit; after ferric chloride dosing began, arsenic stayed below the limit for the rest of the year. Iron was removed to low levels, while manganese was only partly removed because chlorine oxidized less than half of the dissolved manganese and the filters retained only the particles. Hardness, sulfate and silica passed through unchanged, and the backwash solids were classed as non-hazardous.
The raw water, the water after the contact tanks, after each filter and the combined filtered water were sampled on 53 occasions over one year, with arsenic speciation on 13 of them.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Total arsenic | As | μg/L | 36.5 | 7.4 | 80% |
| Soluble arsenic | As | μg/L | 37.8 | 6.5 | 83% |
| Particulate arsenic | As | μg/L | 0.7 | 0.9 | 0% |
| Arsenic (III) | As(III) | μg/L | 35.8 | 2 | 94% |
| Arsenic (V) | As(V) | μg/L | 2.1 | 4.5 | 0% |
| Total iron | Fe | μg/L | 540 | 41.8 | 92% |
| Soluble iron | Fe | μg/L | 485 | <25 | |
| Total manganese | Mn | μg/L | 136 | 91.9 | 32% |
| Soluble manganese | Mn | μg/L | 126 | 76.4 | 39% |
| Alkalinity as CaCO3 | Alk | mg/L | 326 | 313 | |
| Ammonia as N | NH3-N | mg/L | 0.7 | ||
| Fluoride | F− | mg/L | 0.4 | 1 | |
| Sulfate | SO42− | mg/L | 123 | 122 | 0.8% |
| Orthophosphate as PO4 | PO43− | mg/L | <0.1 | 0.07 | |
| Silica as SiO2 | SiO2 | mg/L | 28.7 | 28.8 | 0% |
| Nitrate as N | NO3-N | mg/L | <0.04 | <0.04 | |
| Turbidity | NTU | 6.3 | 0.3 | 95% | |
| pH | 7.5 | 7.4 | |||
| Temperature | °C | 9.1 | 8.9 | ||
| Dissolved oxygen | DO | mg/L | 1.7 | 1.5 | |
| Redox potential | ORP | mV | -77 | 268 | |
| Free chlorine as Cl2 | Cl2 | mg/L | 0.9 | ||
| Total chlorine as Cl2 | Cl2 | mg/L | 1.9 | ||
| Total hardness as CaCO3 | TH | mg/L | 231 | 232 | 0% |
| Calcium hardness as CaCO3 | mg/L | 151 | 153 | 0% | |
| Magnesium hardness as CaCO3 | mg/L | 79.8 | 78.8 | 1.3% |
Inlet: raw well water at the plant inlet. Outlet: combined outlet of the pressure filters. Averages over one year of operation. The inlet averages cover the whole year; the filter outlet averages for arsenic, iron and manganese are those after supplemental iron addition started, and the other outlet averages cover the whole year. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.