    Arsenic and antimony removal from school well water by point-of-entry reverse osmosis

    A school in Carmel, Maine, serving nearly 200 students and teachers, draws water from two wells with elevated arsenic and antimony and uses about 6.6 m³ of water a day. To avoid treating the whole supply, the building was given dual plumbing and a reverse osmosis system placed after an existing storage tank treats only the drinking water line for kitchens, fountains and cold taps. After the membranes the water passes a calcite tank, two storage tanks and a re-pressurization system and is chlorinated before the drinking water line; reject water goes to the existing septic system.

    Treatment line

    1. 01Sediment filterA 5 micron sediment filter ahead of the membranes.
    2. 02Reverse osmosisTwo thin-film composite membrane modules with a booster pump and a dissolved solids monitor, rated at about 4.5 m³ a day.

    What the source found

    The membranes removed arsenic, antimony, sulfate and hardness by more than 99% and dissolved solids by 97%, with silica and alkalinity also strongly reduced. The permeate was slightly acidic and was brought back up by the calcite tank. Treating only the drinking water line with a smaller unit cost less than the originally proposed system for the whole supply, mainly because an existing building could house it and less reject water went to the existing septic system.

    Samples at the combined well header and after the membrane unit at 21 events over 8 months.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.96.9
    Total arsenicAsµg/L18.10.199.4%
    Arsenite, As(III)As(III)µg/L0.2
    Total antimonySbµg/L10.8<0.1
    SulfateSO42−mg/L9.8<0.1
    SilicaSiO2mg/L11.20.596%
    Alkalinity as CaCO3Alkmg/L2065.6
    Total dissolved solidsTDSmg/L2558.697%
    Hardness as CaCO3THmg/L2171.299.4%

    Inlet: well water at the combined well header. Outlet: permeate after the reverse osmosis unit, before the calcite filter. Averages of 21 sampling events (13 weekly and 8 monthly) over 8 months. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.