Aguato

    Arsenic and iron removal from well water by chlorination and pressure filtration

    The municipal water system of Sabin, Minnesota, serving about 500 people, has two wells with arsenic, iron and manganese in the groundwater; only one of them was connected to the new treatment system. The system, designed for about 57 m³/h, started up in January 2006 to lower arsenic using the natural iron already in the water, and it produced on average about 124 m³ of drinking water a day. Treated water goes to an underground clearwell and then to the town's water tower.

    Treatment line

    1. 01PrechlorinationSodium hypochlorite oxidises dissolved arsenic and iron; the dose was later raised to oxidise manganese too.
    2. 02Contact tanksTwo parallel tanks of about 3.2 m³ each giving about 7 minutes for iron flocs to form and take up arsenic.
    3. 03Pressure filtersTwo parallel tanks with a 0.6 m bed of fine ceramic media, backwashed automatically with air scour.

    What the source found

    From wellhead to combined filter outlet, arsenic fell by 80%, iron by 94% and turbidity by 97%, while manganese fell by only 42% because chlorine oxidised it poorly; dissolved solids, silica, sulfate and organic carbon changed little. Three arsenic results above the drinking water standard came from iron and arsenic particles breaking through the filters, so filter runs were shortened. Raising the chlorine dose improved manganese removal but meant even shorter filter runs, and customers reported dark solids from their taps after start-up.

    Plant water was sampled 65 times from January 2006 to April 2007 at the wellhead, after the contact tanks and after each filter, with the combined filter outlet sampled only seven times because its tap worked only from September 2006; distribution system and backwash water were also sampled.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Total arsenicAsµg/L41.88.380%
    Soluble arsenicAsµg/L39.3587%
    Particulate arsenicAsµg/L33.30%
    Arsenic (III)As(III)µg/L11.61.191%
    Arsenic (V)As(V)µg/L27.83.986%
    Total ironFeµg/L1,35087.294%
    Soluble ironFeµg/L1,153<25
    Total manganeseMnµg/L34119842%
    Soluble manganeseMnµg/L35719246%
    Alkalinity as CaCO3Alkmg/L310320
    Ammonia as NNH3-Nmg/L0.20.150%
    FluorideF−mg/L0.10.2
    SulfateSO42−mg/L456453
    Nitrate as NNO3-Nmg/L<0.05<0.05
    Total phosphorus as PTPµg/L30.410.1
    Silica as SiO2SiO2mg/L29.929
    TurbidityNTU19.60.697%
    Total organic carbonTOCmg/L1.71.70%
    Total dissolved solidsTDSmg/L948870
    pH7.37.3
    Temperature°C12.711.8
    Dissolved oxygenDOmg/L3.43.1
    Redox potentialORPmV253481
    Free chlorine as Cl2Cl2mg/L0.3
    Total chlorine as Cl2Cl2mg/L0.6
    Total hardness as CaCO3THmg/L692707
    Calcium hardness as CaCO3mg/L407404
    Magnesium hardness as CaCO3mg/L285303

    Inlet: raw well water at the wellhead. Outlet: combined outlet of the pressure filters. Averages over January 2006 to April 2007; inlet up to 65 samples, combined filter outlet 7 samples from September 2006. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.