Hardness and iron removal from groundwater for 1,300 people by aeration, filters and softening
A small community water system in Illinois with 620 connections serving about 1,300 people treats very hard groundwater from three wells that also carries iron and ammonia. The plant is rated at 1,270 m³ a day and runs 10 to 12 hours a day. It was built to remove iron, manganese and hardness, and it is the only one of the plants studied that does not add chlorine before its filters.
Treatment line
- 01Aeration
- 02Detention
- 03Filters
- 04Three ion exchange softenersRegenerated with brine every 190 m³; part of the filtered water bypasses them and is blended back.
- 05Fluoride addition
- 06Chlorine additionDisinfection of the blended water.
- 07Polyphosphate addition
What the source found
The plant reduced hardness and removed nearly all of the iron and most of the manganese. Some ammonia was converted to nitrate before the softeners, probably biologically since no chlorine was added upstream, and the softener removed most of the rest during routine sampling, but late in a service cycle the softener released ammonia above the raw water level. The chlorine residual in finished water varied widely, possibly because the plant operated near the breakpoint as ammonia changed.
Monthly samples of raw water and finished water (after blending and chlorination) over 6 months, with extra samples after a softener across one service cycle.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 7.97 | 7.82 | |||
| Alkalinity as CaCO3 | Alk | mg/L CaCO3 | 465 | 467 | |
| Hardness as CaCO3 | TH | mg/L CaCO3 | 322 | 72 | 78% |
| Calcium | Ca | mg/L | 78.5 | 12.9 | 84% |
| Magnesium | Mg | mg/L | 30.6 | 9.6 | 69% |
| Iron | Fe | mg/L | 2.11 | 0.02 | 99.1% |
| Manganese | Mn | mg/L | 0.044 | 0.011 | 75% |
| Arsenic | As | µg/L | 0.4 | <0.35 | |
| Potassium | K | mg/L | 17.3 | 7.9 | 54% |
| Total ammonia nitrogen (free and combined in chloramines) | NH3-N | mg N/L | 2.09 | 0.46 | 78% |
| Free ammonia nitrogen | NH3-N | mg N/L | 2.09 | 0.08 | 96% |
Inlet: raw well water. Outlet: finished water after blending of softened and bypass water and chlorination. Averages of 7 monthly samples over 6 months. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.