Aguato

    Hardness and iron removal from groundwater for 500 people by aeration, filters and softening

    A small community water system in Illinois with 200 connections serving about 500 people treats very hard groundwater from two wells that also carries iron, arsenic and high ammonia. The plant is rated at 550 m³ a day and runs 7 to 10 hours a day. It was built to remove iron, manganese, arsenic and hardness.

    Treatment line

    1. 01Aeration
    2. 02Chlorine additionChlorine is added before the filters to oxidize iron, manganese and arsenic.
    3. 03DetentionA detention step after chlorination.
    4. 04Filters
    5. 05Ion exchange softenerOne softener regenerated with brine every 170 to 210 m³; part of the filtered water bypasses it and is blended back.
    6. 06Caustic soda addition
    7. 07Fluoride addition
    8. 08Chlorine additionFinal disinfection of the blended water.

    What the source found

    The plant reduced hardness and removed most of the iron and arsenic, although finished water iron was sometimes above the secondary limit. Ammonia was not reliably removed: in finished water it swung from well below to above the raw water level, likely because a softener takes up ammonia early in a service cycle and can release it late in the cycle. No free chlorine was found in the finished water and the chloramine residual was sometimes very low, so ammonia should be considered when setting regeneration frequency or adding a separate ammonia treatment step.

    Monthly samples of raw water and finished water (after blending and chlorination) over 6 months, plus samples after the softener across one service cycle; this plant had no tap for the routine after-softener sample.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.528.13
    Alkalinity as CaCO3Alkmg/L CaCO3430436
    Hardness as CaCO3THmg/L CaCO32207168%
    CalciumCamg/L49.815.968%
    MagnesiumMgmg/L23.47.568%
    IronFemg/L3.150.197%
    ManganeseMnmg/L0.0280.0164%
    ArsenicAsµg/L18.33.581%
    PotassiumKmg/L2.2155%
    Total ammonia nitrogen (free and combined in chloramines)NH3-Nmg N/L5.24.45
    Free ammonia nitrogenNH3-Nmg N/L5.24.45

    Inlet: raw well water. Outlet: finished water after blending of softened and bypass water and chlorination. Averages of 5 to 6 monthly samples over 6 months. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.