Water tools
Ozone: transferred dose, CT from a decaying residual, and the dose for a coliform target
Ozone is made on site, transferred into the water at less than full efficiency, satisfies an immediate demand, and then decays while it disinfects. Each step is a short calculation.
Contactors reach 90 to 99%.
How it works
For wastewater coliform the ozone response follows a log-log form whose intercept equals the initial demand:
- ozone transferred into the water, mg/L
- gas and water flow, L/min
- ozone in feed gas and off-gas, mg/L
- transfer efficiency, fraction
- residual after time t, mg/L
- residual leaving the dosing zone, mg/L
- decay constant, 1/min
- dose delivered, mg·min/L
- coliform after and before
- utilised ozone dose, mg/L
- initial ozone demand, mg/L
- slope of the dose response
- applied dose, mg/L
No CT credit is taken in the dosing compartment. Decay is faster at high pH, high organic carbon and high temperature, and slower with high alkalinity. Bench units must match the full-scale dosing-compartment residence time; dispersion in the contactor is handled separately. Over-dosing raises bromate.
Related reading
These calculators use standard published formulas and are provided for preliminary engineering guidance. Confirm against measured data and vendor projections before design. Model your full water matrix in Nepti or post your project to compare provider proposals.