Aguato

    Disinfection contactor: pipeline dispersion and serpentine basin t10

    A contactor that lets some water through early gives that water less than its CT. Dispersion measures the spread; the higher the log goal, the less of it you can afford.

    Inputs

    m³/d
    min
    m
    At least 20, preferably 40, for baffled reuse contactors.
    3 for a good design, 7 for a typical older basin, up to 15.
    Pipe diameter0.81mResults

    Results

    Goal

    Allowable dispersion number for the goal
    0.0060

    Pipeline

    Pipe diameter
    0.81m
    Velocity
    0.56m/s
    Dispersion number
    OK: 0.00010

    Within the allowance: close to plug flow.

    Serpentine basin

    Dispersion number
    Caution: 0.0105
    t10 / mean residence time
    0.73
    t10 for credit
    21.9min

    How it works

    Pipeline: diameter from the residence time, dispersion by the field-fitted relation:

    D=4QτπLd=89,500f3.6(DL)0.859(1)

    Serpentine basin: dispersion from the aspect ratio and the ideality coefficient, and the t10 ratio from the aspect ratio:

    d=0.14CiβLt10τ=0.198lnβL−0.002(2)
    where
    D
    pipe diameter, m
    Q
    flow, m³/s
    τ
    residence time, s
    L
    pipe length, m
    d
    dispersion number
    f
    friction factor
    Ci
    coefficient of ideality
    βL
    basin length to width ratio
    t10
    time for the first tenth of a tracer to appear

    The allowable dispersion is where a first-order process falls 5% short of its goal: about 0.03 at 1 log, 0.006 at 4 log. Regulators credit the t10, the time for the first tenth of a tracer to appear, which is conservative against a full residence-time model. Keep the flow-path width constant through 180 degree turns and add diffuser walls at inlet and outlet; up to 40% of a badly baffled tank can be dead volume. The t10 relation holds for aspect ratios of about 5 to 100.

    These calculators use standard published formulas and are provided for preliminary engineering guidance. Confirm against measured data and vendor projections before design. Model your full water matrix in Nepti or post your project to compare provider proposals.