COD and heavy metal removal from pig farm wastewater by drum filter, biodigester and ponds
A pig farm in Yucatan state with capacity for 40,000 fattening pigs a year, over a karst aquifer that is easily polluted. The treated water is used to irrigate pasture on the farm.
Treatment line
- 01Two homogenizing sumps
- 02Drum filterRemoves biosolids.
- 03Parallel biodigesterAnaerobic digestion stage.
- 04Three stabilization ponds in seriesThe third pond has an ozone disinfection system.
What the source found
Over the whole line, COD fell by 96%, suspended solids by 98%, copper by 98%, zinc by 95%, nickel by 73% and chromium by 78%. All metals met the national discharge limits, but suspended solids and COD in the irrigation water stayed well above them. Copper and zinc built up strongly in the irrigated soil compared with natural soil on this farm, one of the two with the simplest treatment.
Daily composite samples on three days of the week, three per point, of the raw wastewater in the collection tank, the water after the biodigester and the water sent to irrigation.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 7.34 | 8.43 | |||
| Arsenic | As | mg/L | <0.01 | <0.01 | |
| Cadmium | Cd | mg/L | 0.0026 | <0.002 | |
| Copper | Cu | mg/L | 29 | 0.59 | 98% |
| Chromium | Cr | mg/L | 0.05 | 0.011 | 78% |
| Nickel | Ni | mg/L | 0.22 | 0.06 | 73% |
| Lead | Pb | mg/L | <0.005 | <0.005 | |
| Zinc | Zn | mg/L | 22 | 1.005 | 95% |
| Mercury | Hg | mg/L | <0.0004 | <0.0004 | |
| Settleable solids | mg/L | 217 | 0.3 | 99.9% | |
| Total suspended solids | TSS | mg/L | 8,300 | 177 | 98% |
| COD | COD | mg/L | 25,980 | 966 | 96% |
Inlet: raw wastewater in the collection tank. Outlet: water sent to irrigation. Means of three daily composite samples per point, taken on three days of the week. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.