COD and oil removal from refinery wastewater by a bench activated sludge reactor
A large oil refinery in Alexandria, Egypt, processing several crude blends treats its wastewater by gravity oil separators, an equalization basin, flotation and activated sludge, and its existing activated sludge stage showed low to moderate removal. Wastewater taken after the oil separators and equalization basin was treated in a bench activated sludge reactor seeded with sludge from a refinery aeration basin, as a baseline for a reactor improved with a magnetite and silica nanocomposite.
Treatment line
- 01Sequencing batch activated sludge reactorA 25 cm PVC basin used both for aeration and, with the air off for 30 to 60 minutes, as the settling clarifier, with treated water drawn from an upper tap each day.
What the source found
The plain activated sludge reactor removed at best 40% of COD, 50% of BOD, 55% of suspended solids, 57% of oil and grease and 13% of dissolved solids, and suspended solids, BOD, COD and oil all stayed above the discharge limits. This is attributed to the toxicity of the oil to the bacteria, the strength of the wastewater and the lack of primary settling. Adding the nanocomposite to the same reactor gave much better removal in a shorter time.
Daily samples of the treated water over a 13 day run on refinery wastewater, compared with the raw wastewater fed to the reactor. The removal figures are the highest reached during the run.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Temperature | °C | 20.8 | 20.0 to 21.7 | ||
| pH | 7.21 | 7.11 to 7.24 | |||
| Dissolved oxygen | DO | mg/l | 4.8 | 4.4 to 5.6 | |
| Total suspended solids | TSS | mg/l | 300 | 134 | 55% |
| Total dissolved solids | TDS | mg/l | 3,100 | 2,710 | 13% |
| BOD | BOD | mg/l | 1,200 | 600 | 50% |
| COD | COD | mg/l | 2,342 | 1,400 | 40% |
| Oil and grease | O&G | mg/l | 380 | 164 | 57% |
Inlet: raw oily refinery wastewater fed to the reactor. Outlet: treated water drawn from the activated sludge reactor. Raw wastewater and the treated water on the day of highest removal in a 13 day run (second trial, unmodified activated sludge). Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.