COD removal from rural town sewage by trickling filters and oxidation ponds
A rural sewage works in Malamulele, Limpopo Province, treats sewage from the town centre and nearby communities and discharges to a river. It is designed for 3000 m³/day and is overloaded.
Treatment line
- 01Manual screening chamberPretreatment of the incoming sewage.
- 02Trickling filters (biofilters)
- 03Oxidation ponds
- 04Chlorine disinfectionChlorine dosed into the final effluent before release to the river.
What the source found
The works removed most of the COD each month, but the final effluent still exceeded the national guideline for COD, ammonia, phosphate and conductivity for most of the period. The plant is overloaded, and the effluent is judged not to be of acceptable quality.
Monthly samples of the influent and the final effluent, and of the river above and below the outfall, from June to October 2024; the removal figures are from the June sampling.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Temperature | °C | 21.9 | 18.8 | ||
| pH | 7.64 | 7.54 | |||
| Dissolved oxygen | DO | ppm | 0 | 2.15 | |
| Total dissolved solids | TDS | mg/L | 365 | 200 | 45% |
| Electrical conductivity | EC | uS/cm | 570 | 312 | |
| Turbidity | NTU | 15.3 | 14.3 | 6.5% | |
| Ammonia | NH3 | mg/L | 68.2 | 9.8 | 86% |
| Nitrate | NO3− | mg/L | 26.5 | 1 | 96% |
| Nitrite | NO2− | mg/L | 26.5 | 1 | 96% |
| Phosphate | PO43− | mg/L | 10.8 | 9.8 | 9.3% |
| Sulfate | SO42− | mg/L | 19.5 | 38.5 | 0% |
| Free chlorine | Cl2 | mg/L | 0.01 | 0.25 | |
| Total chlorine | Cl2 | mg/L | 0 | 0.18 | |
| Chloride | Cl− | mg/L | 23.6 | 21.2 | 10% |
| Alkalinity | Alk | mg/L | 130 | 165 | |
| COD | COD | mg/L | 713 | 48 | 93% |
Inlet: raw sewage at the plant inlet. Outlet: final effluent after chlorination. One grab sample of the influent and of the final effluent in June 2024. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.