    COD removal from sewage with industrial effluent by activated sludge and trickling filters

    A municipal treatment works in Vereeniging, Gauteng, built in 1958 for 83,050 population equivalents, serving local communities and nine large industrial users such as battery, chemical, metal, car wash and food plants, whose effluent makes up about a tenth of the inflow. It receives about 42,000 m³/day against a design capacity of 36,000 m³/day, and storm water and leaking pipes are estimated to add two fifths of the inflow. Treated effluent is discharged to a river.

    Treatment line

    1. 01Pre-treatmentScreening, grit removal and separation of fats, oil and grease.
    2. 02Primary settling tanksRemove smaller particles.
    3. 03Multistage activated sludge with biological nutrient removalInstalled for 20,000 m³/day but treating most of the flow because many trickling filters were out of service.
    4. 04Trickling filtersInstalled for 16,000 m³/day but receiving only about 2,000 m³/day because of ageing equipment and poor maintenance.
    5. 05Anaerobic digestionPart of the secondary treatment stage.
    6. 06ChlorinationThe only tertiary step, for disinfection before discharge.

    What the source found

    The works removed 92% of COD on average, but effluent COD exceeded the national guideline in some months and dissolved salts stayed above the permitted levels. Copper, zinc and lead were not significantly lower in the effluent than in the inflow. The overloading and a high share of poorly biodegradable organic matter in the inflow were judged to explain the poor treatment, and pre-treatment by the industries was recommended.

    Triplicate samples of the plant inflow and final effluent, and of five industrial discharges to the sewer, collected between January and September 2017 across the seasons.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Temperature°C21.622.7
    pH8.38
    BODBODmg/L3.33.8
    Dissolved oxygenDOmg/L1.42.7
    CODCODmg/L4343692%
    Total dissolved solidsTDSmg/L335258
    Electrical conductivityECmS/cm590469
    Salinitypsu0.340.26
    AluminiumAlmg/L0.180.2
    ZincZnmg/L0.20.16
    CopperCumg/L0.220.18
    LeadPbmg/L0.20.19

    Inlet: plant inflow. Outlet: final effluent of the plant. Means of triplicate samples collected across the seasons between January and September 2017. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.