COD and ammonia removal from municipal sewage by activated sludge and chlorination
A municipal activated sludge works in the North West Province serving a town of about 124 000 people that is an industrial and agricultural growth point, so it takes domestic sewage strongly influenced by household and industrial water use. The works is not connected to the stormwater system, yet its inflow rose in the wet season, which was put down to vandalised sewer manholes. Treated effluent is discharged to a river.
Treatment line
- 01Preliminary treatment
- 02Primary treatment
- 03Secondary activated sludgeRun in Phoredox and Bardenpho configurations; a Modified UCT configuration was switched to Phoredox in October 2019.
- 04ChlorinationChlorine gas dosed at a constant rate in all seasons, with 30 minutes of contact time at the tertiary stage.
What the source found
In the dry season the works removed about 96% of COD and above 99% of ammonia, while nitrate did not fall and rose slightly across the plant. Ammonia removal weakened in the wet season, and the final effluent met the general discharge limits for most parameters but often fell short of the stricter special limits, above all for nitrate and E. coli. Chlorination alone was judged not enough to meet the special limit for E. coli.
Samples taken at the raw inlet and the final effluent over a dry and a wet season; the figures shown are the averages of the five dry-season months, May to September 2019.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| E. coli | count/100 mL | 51 | |||
| Ammonia | NH3 | mg/L | 43.18 | 0.27 | 99.4% |
| COD | COD | mg/L | 719 | 30 | 96% |
| Nitrate | NO3− | mg/L | 8.94 | 9.21 | 0% |
| Orthophosphate | PO43− | mg/L | 5.82 | 0.46 | 92% |
Inlet: raw sewage at the plant inlet. Outlet: final chlorinated effluent. Averages of five monthly dry-season means, May to September 2019. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.