Poultry slaughterhouse water reuse by electrocoagulation, ultrafiltration and reverse osmosis
An industrial-scale plant treats wastewater from defeathering, evisceration and cooling at a poultry slaughterhouse in Izhevsk village, Akmola region, about 70 km from the capital. It runs semi-batch with production; more than half of the feed is recovered as treated water for cooling in the slaughterhouse and the rest goes to the sewer.
Treatment line
- 01Receiving tank with mesh filter1 m³ tank that also serves as primary settling and cooling, with a mesh screen above it and a flow meter in front.
- 02Feather catcher
- 03Fat catcher
- 04Coarse mechanical filtration1 mm mesh fed by a rotary pump; the retained solids go to the sewer.
- 05Electrocoagulation reactorAluminium anodes and graphite cathodes in a chamber of about 1.0 by 0.8 by 1.5 m, the main pre-treatment before the membranes.
- 06UltrafiltrationOne cartridge-type module with 0.02 µm pores.
- 07Reverse osmosisOne module rated at 1 m³/h of permeate; the concentrate goes to the sewer or is reused for cooling.
What the source found
The whole line removed above 99% of COD, BOD, suspended solids and nickel, 96% of manganese, 94% of chromium and aluminium and 92% of iron, keeping near-complete removal of organics and solids for six months. Electrocoagulation took out most solids, organics, iron and aluminium but little of the nutrients, which the membranes then removed; colour and chromium in the permeate still did not meet drinking water guidelines. Membrane cake built up slowly thanks to the pre-treatment, and reverse osmosis used about twice the energy of ultrafiltration.
Grab samples of the raw wastewater, the electrocoagulation effluent and the final membrane permeate from September 2019 to February 2020, with twelve samples of the raw wastewater, and membrane cake thickness measured over the six months.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 7.13 | 7.95 | |||
| Turbidity | FAU | 259.62 | 0.32 | 99.9% | |
| Colour | degree | 3,147.83 | 8.83 | 99.7% | |
| Total suspended solids | TSS | mg/L | 452.67 | 1.33 | 99.7% |
| Free chlorine | Cl2 | mg/L | 0.23 | 0.02 | 91% |
| Total chlorine | Cl2 | mg/L | 0.28 | 0.02 | 93% |
| Nitrite | NO2− | mg/L | 0.16 | 0 | |
| Nitrate | NO3− | mg/L | 17.01 | 1.18 | 93% |
| Phosphate | PO43− | mg/L | 3.82 | 0.12 | 97% |
| Ammonium | NH4+ | mg/L | 13.5 | 0.18 | 99% |
| Total iron | Fe | mg/L | 0.9 | 0.07 | 92% |
| Aluminium | Al | mg/L | 0.78 | 0.05 | 94% |
| COD | COD | mg/L | 3,527.17 | 8.46 | 99.8% |
| BOD | BOD | mg/L | 1,321.33 | 3.97 | 99.7% |
| Chromium | Cr | mg/L | 1.19 | 0.07 | 94% |
| Nickel | Ni | mg/L | 7.53 | 0.02 | 99.7% |
| Manganese | Mn | mg/L | 0.72 | 0.03 | 96% |
Inlet: raw slaughterhouse wastewater. Outlet: membrane permeate after ultrafiltration and reverse osmosis. Arithmetic means of grab samples (12 of the raw wastewater) from September 2019 to February 2020. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.