Aguato

    COD and BOD removal at a buffalo abattoir by chemical dosing, settling and activated sludge

    A buffalo abattoir at Bhoor Garhi, Dasna, Ghaziabad district, Uttar Pradesh, has capacity to slaughter 750 buffalo a day and produces frozen meat with meat bone, tallow and blood meal by-products. Its effluent treatment plant covers 1,900 m², is designed for 750 m³/day and treated on average 353 m³/day while it was monitored. Treated water is reused for rendering and floor washing and used for irrigation, cooling and landscaping.

    Treatment line

    1. 01Oil and grease trap tanksFour tanks of 17.1 m³.
    2. 02Holding tanksThree tanks of 131.8 m³.
    3. 03Equalisation tanksTwo tanks of 22.5 m³.
    4. 04Solid separators and screensTwo units.
    5. 05Chemical dosing tanksTwo tanks of 39.1 m³.
    6. 06Primary settling tank7.31 m diameter, 168 m³.
    7. 07Two aeration tanks in seriesActivated sludge: the first tank takes BOD shock loads and the second polishes.
    8. 08Secondary clarifiersTwo clarifiers of 168 m³.
    9. 09Disinfection tank55 m³.
    10. 10Treated water tank382 m³.
    11. 11Sand filter5.5 m³.
    12. 12Activated carbon filter5.5 m³.

    What the source found

    The plant removed 95% of COD, 98% of BOD, 99% of suspended solids, 77% of oil and grease and 97% of ammonium nitrogen, with strong nitrification, and it performed well for carbon and nitrogen removal. The wastewater was short of phosphorus for the biology, and the sand and carbon filters polished less than intended, which points to lower filtration rates.

    Replicate samples from the inlet, the stages of the plant and the final outlet were analysed in a university laboratory, with on-site checks of the aeration tank sludge.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH7.927
    TurbidityNTU30011.396%
    AlkalinityAlkmg/L743.333348
    Oil and greaseO&Gmg/L18041.9377%
    BODBODmg/L1,327.66725.398%
    CODCODmg/L1,737.66785.395%
    Total suspended solidsTSSmg/L2,04826.9799%
    Ammonium nitrogenNH4-Nmg/L155.86673.9398%
    Nitrate nitrogenNO3-Nmg/L3.888.50%
    Orthophosphate as phosphorusPO4-Pmg/L12.82.7

    Inlet: raw effluent at the treatment plant inlet. Outlet: final treated effluent. Averages of replicate samples during monitoring of the plant. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.