Copper removal from dairy wastewater by screening, equalisation and coagulation-flocculation
A dairy factory in Adelândia, Goiás, treats its effluent in a plant with a bar screen, an equalisation tank, three physico-chemical tanks and one biological tank. The figures here cover the raw effluent up to the outlet of the physico-chemical section; the biological stage with its aeration tank and secondary clarifier, and the factory's own domestic sewage added to the stream, come after it.
Treatment line
- 01ScreensBar screen ahead of the equalisation tank.
- 02Equalisation tankReceives the raw effluent before chemical treatment.
- 03Three physico-chemical tanksCoagulation and flocculation, with removal of the solids formed.
What the source found
Copper fell by 53% across the physico-chemical stage, zinc by 13% and lead by 8%, which is linked to the removal of suspended solids by coagulation and flocculation. All metals stayed below the state discharge limits. The works as a whole did not reduce COD, BOD or total solids, which rose along the line: the solids formed in coagulation were not removed well and carried over, and the final effluent stayed toxic to fish.
Six sampling campaigns from April 2010 to April 2011; the metal figures are means of four samples of the raw effluent and of the effluent after the physico-chemical stage.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Cadmium | Cd | mg.L-1 | 0.005 | 0.005 | |
| Lead | Pb | mg.L-1 | 0.037 | 0.034 | 8.1% |
| Copper | Cu | mg.L-1 | 0.459 | 0.217 | 53% |
| Zinc | Zn | mg.L-1 | 0.271 | 0.235 | 13% |
| COD | COD | mg.L-1 | 2,656.32 | 13,074.43 | |
| BOD | BOD | mg.L-1 | 1,932.07 | 2,034.35 | |
| Total solids | TS | mg.L-1 | 2,295 | 13,961 | |
| Oil and grease | O&G | mg.L-1 | 55.1 | 82.2 | |
| pH | 4.3 | 2.88 | |||
| Turbidity | NTU | 578 | 930 | 0% | |
| Total dissolved solids | TDS | mg.L-1 | 1,720 | 3,495 | 0% |
| Salinity | 0.8 | 1.8 | |||
| Electrical conductivity | EC | µS.cm3 | 1,740 | 3,425 | |
| Dissolved oxygen | DO | mg.L-1 | 3.9 | 0.7 | |
| Temperature | oC | 26.2 | 26.9 |
Inlet: raw effluent before treatment. Outlet: effluent after the coagulation and flocculation stage. Means of four samples of each point taken between April 2010 and April 2011. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.