    BOD and COD removal from dairy wastewater by combined anaerobic and aerobic treatment

    The effluent treatment plant serves a large food and dairy manufacturer in Vulta, Rupganj, Narayanganj, Dhaka, Bangladesh. It has a capacity of 48 m³ a day and was designed for wastewater high in organic matter and suspended solids, which it must bring within the national discharge standards.

    Treatment line

    1. 01Combined anaerobic and aerobic biological treatmentThe plant combines anaerobic and aerobic processes.

    What the source found

    The plant met the discharge standards for all measured parameters in all three seasons, with removal varying by only a few points between seasons. Averaged over the three seasons it removed 98% of BOD, 97% of COD and 91% of suspended solids. Laboratory jar tests on the raw wastewater found lime with ferrous sulfate to be the best of the chemical pretreatment options tested.

    Grab samples from the inlet and final outlet drains during peak production hours on three dates in different seasons, in September 2022, November 2022 and May 2023.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH6.077.45
    BODBODmg/L1,2982898%
    CODCODmg/L2,2216697%
    Total dissolved solidsTDSmg/L9056893%
    Total suspended solidsTSSmg/L5123493%

    Inlet: inlet drain of the effluent treatment plant. Outlet: final outlet drain of the effluent treatment plant. Grab samples in peak production hours on one summer day in May 2023. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.