Aguato

    COD and phosphorus removal from winery wastewater by a three-stage constructed wetland

    A winery in Castellina in Chianti that only bottles and ages wine produces wastewater from washing bottles, tanks, silos and floors. A constructed wetland plant has served it since 2001 and was upgraded in 2009 when production doubled; it is designed for up to 100 m³ a day and treated about 60 m³ a day on average. The treated water is discharged to a river and must meet national limits for industrial discharge to surface water.

    Treatment line

    1. 01Equalisation tank70 m³; three pumps in it feed the first-stage beds in batches.
    2. 02French reed beds1,200 m² in three lines fed in turn, 3 hours on and 6 hours resting, planted with common reed.
    3. 03Horizontal subsurface flow wetland960 m² in four parallel sectors, fed by gravity and planted with common reed.
    4. 04Free water surface wetland850 m² in five cells in series with native aquatic plants and a design retention time of 3.3 days.
    5. 05Sand filterOptional 50 m² post-treatment that the final effluent can be pumped to.

    What the source found

    The plant met its discharge limits for every monitored parameter over the two and a half years, with mean removal of 98% for COD and 46% for total phosphorus. The reed beds did most of the COD removal, but the later wetland stages were needed to reach the limit, and the sand filter was needed only once. The online sensor followed the rise and fall of effluent COD well but tended to read low, so it cannot fully replace laboratory samples.

    Monthly grab samples at the inlet and after each stage from January 2017 to June 2019, a few samples a year by the regional control authority, and an online COD sensor reading the final effluent every 30 minutes.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    pH6.88.1
    CODCODmg/L1,1592998%
    Nitrite nitrogenNO2-Nmg/L0.240.0483%
    Nitrate nitrogenNO3-Nmg/L1.30.839%
    Total phosphorusTPmg/L7.23.946%
    Anionic surfactants (MBAS)mg/L30.293%

    Inlet: raw winery wastewater at the plant inlet. Outlet: final effluent after the optional sand filter. Means of monthly grab samples from January 2017 to June 2019 (29 inlet and 37 to 38 outlet samples). Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.