High-rate trickling filter sizing
Trickling filters are sized on organic loading and checked on hydraulic loading. The NRC relation then predicts the removal, which you compare with the effluent target.
Inputs
Results
Filter
- Media volume
- 371m³
- Total area
- 185m²
- Diameter per unit
- 10.9m
- Hydraulic loading, average
- 16.2m³/m²·d
- Hydraulic loading, max day
- 19.4m³/m²·d
- Hydraulic loading, max hour
- 29.1m³/m²·d
Performance
- BOD₅ removal (NRC)
- 71%
- Effluent BOD₅
- 30mg/L
Sludge
- Sludge produced
- 168kg TSS/d
- Volatile sludge
- 126kg VSS/d
- Sludge volume
- 16.4m³/d
How it works
Media volume from the organic loading, area from the depth, then hydraulic loading as a check:
Removal by the NRC relation with the recirculation factor:
- media volume, m³
- flow, m³/d
- influent BOD₅, kg/m³
- volumetric organic loading, kg BOD₅/m³·d
- filter area, m²
- packing depth, m
- hydraulic loading, m³/m²·d
- BOD₅ removal, %
- recirculation factor
- recycle ratio
- effluent BOD₅, mg/L
- sludge produced, kg TSS/d
- sludge yield, kg TSS per kg BOD₅ removed
- sludge volume, m³/d
- sludge density, about 1,020 kg/m³
- settled sludge solids, fraction
The NRC relation was developed for stone beds fed settled wastewater; for anaerobic effluents it should be used with caution. Stone media clog at high organic loads; plastic media allow deeper beds and higher loadings. Add a secondary settler at 16 to 32 m³/m²·d average surface loading.
Related reading
These calculators use standard published formulas and are provided for preliminary engineering guidance. Confirm against measured data and vendor projections before design. Model your full water matrix in Nepti or post your project to compare provider proposals.