BOD and COD removal from school grey water by septic tank and vertical flow reed bed
A small constructed wetland built in 2000 at a school in Panauti, Nepal, rated at 0.5 m³ a day and treating grey water. The treated water drains to the environment.
Treatment line
- 01Septic tankSettling tank receiving the raw grey water.
- 02Vertical flow reed bedSub-surface flow bed planted with reeds; treated water is collected in a tank after it.
What the source found
The wetland removed 82% of BOD and 83% of COD, close to the best of the three wetlands surveyed. Phosphorus was barely reduced, which was linked to a bed material poor in the elements that bind it. Wetlands of this kind were judged cost-effective and easy to maintain.
Samples on two occasions at the inlet pipe before the septic tank and at the tank after the vertical flow bed, taken between 7 and 8 in the morning at peak flow.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| pH | 6.7 | 6.3 | |||
| Electrical conductivity | EC | ms/cm | 2.5 | 1.35 | |
| Total suspended solids | TSS | mg/L | 3,830 | 308 | 92% |
| Total dissolved solids | TDS | mg/L | 1,165 | 455 | 61% |
| Total solids | TS | mg/L | 4,995 | 763 | 85% |
| BOD5 | BOD5 | mg/L | 103.5 | 18.5 | 82% |
| COD | COD | mg/L | 205 | 35 | 83% |
| Phosphorus (measured as dissolved orthophosphate) | P | mg/L | 1.04 | 0.98 | 5.8% |
Inlet: raw grey water at the inlet pipe before the septic tank. Outlet: collection tank after the vertical flow bed. Means of two samples taken on two occasions at peak morning flow. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.