Aguato

    BOD and COD removal from domestic sewage by an aerated facultative pond and maturation ponds

    A municipal sewage works in operation since 1997 serving the eastern district of Teresina, Piauí, with domestic sewage pumped in from a lift station on site. It was designed for about 111,000 inhabitants by 2005, but during the study it received an estimated 4,250 to 5,870 m³/day, well below its design flow. The treated effluent is discharged into a river 100 m from the works.

    Treatment line

    1. 01Bar screenFirst part of the preliminary treatment.
    2. 02Grit chambersSand boxes that remove grit after the screen.
    3. 03Aerated facultative pondOne pond of 1.11 ha, 3.5 m deep and 38,880 m³, aerated by ten aerators, with a design retention time of 2 days.
    4. 04Two parallel series of two maturation pondsThe aerated pond effluent splits between maturation ponds 1 then 3 and 2 then 4, each pond 2.3 m deep, about 2.5 ha and 57,000 to 59,000 m³, with design retention times of about 6 days each.

    What the source found

    Over the whole period the works removed on average 80% of BOD and 71% of COD, and in the dry season of 2000 the removals were 84% for BOD and 78% for COD. Total solids were not removed and often rose, which was linked to algae grown in the ponds leaving with the effluent and to storm water entering the sewers. Faecal coliforms fell by 99.9%, and the discharge caused no significant change in river water quality.

    Weekly morning grab samples of raw sewage and final effluent from March 1999 to November 2001, grouped by dry and rainy season; the figures shown are the means for the dry season of 2000.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Temperature°C31.130.8
    pH77.6
    Electrical conductivityECµS/cm543512
    BOD5BOD5mg/L4457284%
    CODCODmg/L65014478%
    Total solidsTSmg/L864511
    Total fixed solidsTFSmg/L220215
    Total volatile solidsTVSmg/L642296
    Faecal coliformsFCMPN/100 mL33,000,00016,000>99.9%

    Inlet: raw sewage at the works inlet. Outlet: final effluent of the pond system. Means of weekly morning grab samples over the dry season of 2000 (June to November). Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.