COD and BOD removal from weak city sewage by extended-aeration activated sludge
A large municipal sewage works in the state of Pernambuco, sized for about 451,000 people, that receives sewage from several districts through a collection network. The sewage takes longer to reach the works than at a small works in the same state, which may lower some of its values on the way.
Treatment line
- 01Grit chamberRaw sewage was sampled at its entrance.
- 02Aeration tankActivated sludge with extended aeration.
- 03Secondary settlerTreated effluent was sampled at its outlet.
What the source found
On the sampling day the works removed about 51% of COD, 68% of BOD, 61% of colour and 62% of turbidity, and met the discharge requirements for domestic sewage. Suspended and total solids were higher at the outlet than at the inlet, which may mean the settler was not working properly. Ammonia rose and nitrate barely changed; the works was not designed to remove nitrogen.
One sample at the grit chamber inlet and one at the secondary settler outlet, taken at the same moment in the dry season of February 2014, without allowing for the retention time.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| COD | COD | mg O2/L | 195 | 96 | 51% |
| BOD5 | BOD5 | mg O2/L | 118 | 38 | 68% |
| Total solids | TS | mg/L | 462.5 | 563 | 0% |
| Fixed solids | FS | mg/L | 322 | 417 | 0% |
| Volatile solids | VS | mg/L | 140.5 | 146 | 0% |
| Total suspended solids | TSS | mg/L | 140 | 218 | 0% |
| Fixed suspended solids | FSS | mg/L | 108 | 198 | 0% |
| Volatile suspended solids | VSS | mg/L | 32 | 20 | 38% |
| Total Kjeldahl nitrogen | TKN | mg/L | 89.26 | 96.7 | 0% |
| Ammonia nitrogen | NH3-N | mg/L | 0.83 | 3.19 | 0% |
| Nitrate nitrogen | NO3-N | mg/L | 0.9 | 0.8 | 11% |
| Electrical conductivity | EC | µS/cm | 561 | 706 | |
| Colour | mg Pt-Co/L | 241 | 95 | 61% | |
| pH | 6.5 | 6.6 | |||
| Dissolved oxygen | DO | mg O2/L | 17.1 | 16.97 | |
| Turbidity | NTU | 102 | 38.4 | 62% | |
| Alkalinity | Alk | mg Ca/L | 197.12 | 250.39 |
Inlet: grit chamber inlet. Outlet: secondary settler outlet. One inlet and one outlet sample taken at the same moment in February 2014, in the dry season. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.