COD and BOD removal from low-income area sewage by UASB reactors and a polishing pond
A sewage works in a low-income area of the Recife metropolitan region, designed for 18,000 people and one of the first full-scale UASB plus polishing pond plants operating in Brazil. Domestic sewage is pumped to a bar screen and grit chamber before the units below, and the treated water is discharged to a drainage channel that runs into a river.
Treatment line
- 01Eight UASB reactors in parallelEach 4.5 by 4.5 by 5.0 m, 810 m³ of working volume in total, with a 7 hour retention time; the flow is split equally between them.
- 02Polishing pondTrapezoidal pond 145 m long and 1.5 m deep, 8,154 m³, with about 3 days of retention.
What the source found
Over this phase the line removed about 75% of COD, 78% of BOD and 73% of suspended solids. The pond added useful removal of organic matter but removed little nitrogen and phosphorus, and the effluent did not meet the thermotolerant coliform standard for unrestricted irrigation. Performance was held back by sand carried from the grit chamber into the reactors, uneven feed distribution, blocked pipes, no routine removal of excess sludge, and a pond that is too small and too deep for its load.
Grab samples at the UASB inlet (after the grit chamber) and at the pond outlet; the figures are the geometric means of 168 samplings over 1,290 days of one publicly operated phase within 13 years of monitoring from December 1997 to April 2010.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Temperature | 29 | 29 | |||
| pH | 6.9 | 7.7 | |||
| Alkalinity | Alk | mg/L CaCO3 | 306 | 249 | |
| Chloride | Cl− | 161 | 125 | 22% | |
| Total solids | TS | mg/L | 912 | 573 | 37% |
| Total fixed solids | TFS | 553 | 389 | 30% | |
| Total volatile solids | TVS | 321 | 155 | 52% | |
| Total suspended solids | TSS | mg/L | 214 | 58 | 73% |
| Fixed suspended solids | FSS | 70 | 12 | 83% | |
| Volatile suspended solids | VSS | 137 | 41 | 70% | |
| Sulfate | SO42− | 20 | 28 | 0% | |
| Total BOD | BOD | mg/L | 354 | 77 | 78% |
| Filtered BOD | sBOD | mg/L | 103 | 29 | 72% |
| Total COD | COD | mg/L | 498 | 124 | 75% |
| Filtered COD | sCOD | 114 | 44 | 61% | |
| Total nitrogen | TN | 18 | 14 | 22% | |
| Ammoniacal nitrogen | NH3-N | mg/L | 12 | 9 | 25% |
| Nitrite | NO2− | 0.1 | 0.2 | 0% | |
| Nitrate | NO3− | 0.08 | 0.33 | 0% | |
| Total coliforms | TC | 1,660,000 | 2,740,000 | 0% | |
| Thermotolerant coliforms | FC | MPN/100 mL | 342,000 | 542,000 | 0% |
| Volatile fatty acids | VFA | mg/L | 66 |
Inlet: UASB reactor inlet after the grit chamber. Outlet: polishing pond outlet. Geometric means of 168 grab samplings in one publicly operated phase of the plant's monitoring. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.