Aguato

    BOD and COD removal from strong residential sewage by extended-aeration activated sludge

    A small municipal sewage works in the state of Pernambuco, sized for about 12,000 people, that serves mainly one housing development. The sewage travels only a short distance to the works, so it arrives much stronger than at a large works in the same state, with about five times the COD.

    Treatment line

    1. 01Grit chamberRaw sewage was sampled at its entrance.
    2. 02Aeration tankActivated sludge with extended aeration.
    3. 03Secondary settlerTreated effluent was sampled at its outlet.

    What the source found

    On the sampling day the works removed about 66% of COD and 88% of BOD and met the discharge requirements for domestic sewage. The sewage carried much particulate matter, and the works removed only about 11% of suspended solids, 27% of colour and 41% of turbidity. Nitrate fell by about 96% while ammonia rose slightly, which may point to denitrification; the works was not designed to remove nitrogen.

    One sample at the grit chamber inlet and one at the secondary settler outlet, taken at the same moment in the dry season of January 2014, without allowing for the retention time.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    CODCODmg O2/L1,00634066%
    BOD5BOD5mg O2/L6007088%
    Total solidsTSmg/L88865926%
    Fixed solidsFSmg/L50442216%
    Volatile solidsVSmg/L38423738%
    Total suspended solidsTSSmg/L53047211%
    Fixed suspended solidsFSSmg/L34940%
    Volatile suspended solidsVSSmg/L49637824%
    Total Kjeldahl nitrogenTKNmg/L303.6293.53.3%
    Ammonia nitrogenNH3-Nmg/L0.652.420%
    Nitrate nitrogenNO3-Nmg/L200.996%
    Electrical conductivityECµS/cm884794
    Colourmg Pt-Co/L34024927%
    pH7.67.4
    Dissolved oxygenDOmg O2/L11.57.5
    TurbidityNTU34520341%
    AlkalinityAlkmg Ca/L298.34282.36

    Inlet: grit chamber inlet. Outlet: secondary settler outlet. One inlet and one outlet sample taken at the same moment in January 2014, in the dry season. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair. A parameter at 0% did not fall between the inlet and the outlet.