Sulfide removal from raw sewage in a UASB reactor with low-level aeration
A laboratory UASB reactor at a sewage research station in Campina Grande, Paraíba, fed with raw municipal sewage taken from the city's sewer interceptor. Sulfide formed in anaerobic reactors causes odour and corrosion, so a small amount of air was added to turn sulfide into elemental sulfur or sulfate. The feed of this reactor was spiked with sodium sulfate as an extra sulfate source.
Treatment line
- 01Vertical grit boxReceives the sewage pumped from the municipal interceptor.
- 02Equalisation tank20 litre tank where sodium sulfate is added to the raw sewage.
- 03UASB reactor with low-level aerationY-shaped 10.4 litre reactor with a 12 hour retention time and 20 litres per day of effluent. An air stone moves part of the liquid into a side vessel, where it takes up oxygen, and it returns to the reactor above the sludge blanket.
What the source found
Low aeration above the sludge blanket cut the sulfide leaving the reactor by about 95%, and sulfate fell by about 44% in this stage. Total COD removal in the same stage was 58%. The work concluded that the aerated UASB could be improved further for sulfide oxidation.
Raw sewage from the equalisation tank and reactor effluent were analysed three times a week; the figures are the means of the first of three test stages, each run at a different dissolved oxygen level, starting in October 2014.
Water in, water out
| Parameter | Symbol | Unit | Inlet | Outlet | Removal |
|---|---|---|---|---|---|
| Sulfate as sulfur | SO4-S | mg S-SO4/L | 11.71 | 6.55 | 44% |
| Total dissolved sulfide as sulfur | S2− | mg S-STD/L | 6.87 | 0.32 | 95% |
| Sulfate plus sulfide as sulfur | mg S-S/L | 18.58 | 6.87 | 63% | |
| pH | 7.94 | 8.12 | |||
| Total alkalinity | Alk | mg CaCO3/L | 369.98 | 395.29 | |
| Volatile fatty acids | VFA | mg HAc/L | 71.4 | 18.13 | 75% |
| Total COD | COD | mg/L | 528 | 219 | 59% |
| Filtered COD | sCOD | mg/L | 186 | 149 | 20% |
| Total solids | TS | 1,378.25 | 1,192.2 | 14% | |
| Total volatile solids | TVS | 509.5 | 339.25 | 33% | |
| Total suspended solids | TSS | 285 | 96.5 | 66% | |
| Volatile suspended solids | VSS | 250 | 86.5 | 65% | |
| Dissolved oxygen | DO | mg O2/L | 1.27 |
Inlet: raw sewage with added sodium sulfate from the equalisation tank. Outlet: effluent of the aerated UASB reactor. Means of the analyses made three times a week during the first of three test stages of this reactor, starting in October 2014. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.