    BOD and COD removal from chocolate factory wastewater by coagulation and activated sludge

    A chocolate processing factory in Tangerang Regency, Indonesia, treats wastewater from equipment washing, raw material mixing, cooking, cooling and sanitation of the production area. The water is high in organic matter and is treated before discharge to a receiving water body or reuse. Domestic wastewater joins the line at the second equalisation tank to balance nutrients for the biology.

    Treatment line

    1. 01Equalisation tank 1Receives the production wastewater and evens out flow and load.
    2. 02Chemical treatmentBase, polyaluminium chloride coagulant and flocculant are dosed in sequence.
    3. 03Chemical clarifierSettles the flocs as chemical sludge.
    4. 04Equalisation tank 2Mixed tank that also takes domestic wastewater.
    5. 05Aeration tankActivated sludge with air supplied by blowers.
    6. 06Biological clarifierSeparates the biomass; part of the sludge returns to the aeration tank.
    7. 07Control tankBalancing and monitoring point before tertiary treatment.
    8. 08Sand filterRemoves remaining fine solids.
    9. 09Carbon filterAdsorbs dissolved organics, colour and odour.
    10. 10ChlorinationDisinfection after a flow meter.
    11. 11Effluent tankHolds treated water before discharge or reuse.

    What the source found

    BOD and COD were each cut by 99%, and the treated water met the national discharge standard. Total coliform fell by about 97% across the plant. Removal of BOD and COD stayed above 97% in every month of monitoring.

    Grab samples at the plant inlet and outlet, 33 in total, between October 2025 and April 2026, with mean values reported.

    Water in, water out

    ParameterSymbolUnitInletOutletRemoval
    Temperature°C29.829.8
    Total dissolved solidsTDSmg/l97445254%
    Total suspended solidsTSSmg/l641675%
    pH6.867.19
    Dissolved ironFemg/l0.50.340%
    Dissolved manganeseMnmg/l0.3<0.040
    BariumBamg/l0.5<0.50
    CopperCumg/l0.40.175%
    ZincZnmg/l0.50.260%
    Hexavalent chromiumCr(VI)mg/l<0.10<0.10
    Total chromiumCrmg/l<0.10<0.10
    CadmiumCdmg/l<0.040<0.040
    MercuryHgmg/l<0.0010<0.0010
    LeadPbmg/l<0.10<0.10
    TinSnmg/l<2.0<2.0
    ArsenicAsmg/l<0.002<0.002
    SeleniumSemg/l<0.002<0.002
    NickelNimg/l<0.10<0.10
    CobaltComg/l<0.10<0.10
    CyanideCN−mg/l<0.004<0.004
    Sulfide as H2SH2Smg/l<0.06<0.06
    FluorideF−mg/l1.50.473%
    Free chlorineCl2mg/l<0.03<0.03
    Ammonia nitrogenNH3-Nmg/l0.540.426%
    Nitrate nitrogenNO3-Nmg/l1.340.4864%
    Nitrite nitrogenNO2-Nmg/l<0.010<0.010
    Total nitrogenTNmg/l24675%
    BODBODmg/l1,52412.9499.2%
    CODCODmg/l6,47054.799.2%
    Surfactants as MBASmg/L1.840.3680%
    Phenolmg/L<0.20<0.20
    Oil and greaseO&Gmg/L<5<5
    Total coliformTCMPN/100 ml19,00056097%

    Inlet: raw wastewater at the treatment plant inlet. Outlet: treated water at the treatment plant outlet. Mean values of 33 samples taken from October 2025 to April 2026. Values and units are as the published source prints them. Removal is worked out from the two values, or is the source's own figure where it prints no pair.